Inspect I/U; Inspect I/U (When 1 Or 2 Remote Controls Are Connected) - Mitsubishi Heavy Industries FDT40ZSXW1VH Service Manual

Hyper inverter packaged air-conditioners, split system, air to air heat pump type, ceiling cassette- 4 way type
Table of Contents

Advertisement

Error code
Remote control:

INSPECT I/U

1. Applicable model
All models
2. Error detection method
Communication between
indoor unit and remote control
is disabled for more than 30
minutes after the power on.
3. Condition of error displayed
Same as above
4. Presumable cause
• Improper setting
• Surrounding environment
• Defective remote control
communication circuit
• Faulty indoor unit control
PCB
Note:
If any error is detected 30 minutes after displaying "
"INSPECT I/U".
LED
Green
Red
Keeps flashing Stays OFF
Indoor
5. Troubleshooting
Diagnosis
YES
⑴, ⑵ 
Set one remote control
for "Master" and the other
for "Slave"
Note (1) Use SW1 to set at
master or slave.
Does it
become normal?
NO
Do more than
one indoor units have the
same address?
NO
Are remote
control wires laid
along high voltage
wires?
NO
Disconnect the connecting
wire Ž between the indoor
and outdoor unit.
Power source reset
Does DM
start 60 seconds later
automatically.
WAIT
55
-
Content
INSPECT I/U
(When 1 or 2 remote controls are connected)
Are 2 units
of remote control
connected?
NO
⑵ 
Is it set
at the slave remote
YES
control?
Note (2)
"Slave" is displayed
on the remote
control LCD.
NO
YES
YES
YES
NO
" on the remote control, the display changes to
-
'19 • PAC-SM-302
Countermeasure
Set SW1 on remote control
PCB at "Master".
Set address again. (SW2 on
indoor unit control PCB)
Separate remote control
wires from high voltage
wires.
Defective indoor unit
control PCB ➞ Replace.
Defective remote control
➞ Change.