Overview Of Electrical Connections - Viessmann SDIO Installation And Service Instructions For Contractors

Electronics module
Table of Contents

Advertisement

Installation sequence

Overview of electrical connections

Danger
Incorrect wiring can lead to serious injury from
electrical current and result in appliance dam-
age.
Route extra low voltage (ELV) leads < 42 V
and
42 V/230 V~ cables separately.
>
Only strip the minimum of insulation from
cables as close as possible to the terminals
and bundle tightly to the corresponding termi-
nals.
Secure cables with cable ties.
SDIO/SM1A electronics module
SDIO/SM1A
aVG
%
&
jF
TS1
TS2
aVG
KM-BUS
jF
PLUS-
BUS
Fig. 1
Cylinder temperature sensor, NTC 10 k
%
standard delivery) with plug
Collector temperature sensor, NTC 20 k
&
standard delivery)
Temperature sensor, NTC 10 k
/
delivery)
Temperature sensor, NTC 10 k
delivery)
Transfer pump or 3-way diverter valve
sS
!
Please note
Electronic assemblies can be damaged by static
loads.
Before beginning work, touch an earthed object
such as a heating or water pipe to discharge any
static.
10
/
[{]
PWM
TS3
TS4
L ? N
(TS1,
Ω
%
(TS2,
Ω
(TS3, standard
Ω
(TS4, standard
Ω
F1 T 2 A
sS
sF
L ? N
N
L
?
M
1~
230 V∼
50 Hz
M
1~
Solar circuit pump (only with PWM signal)
sF
Power supply
PlusBus for connection to the HMU heat man-
jF
agement unit, DIO electronics module or ADIO
electronics module
KM-BUS for connection to the Vitotronic boiler
aVG
control unit
PWM Solar circuit pump speed control
Note
Apply strain relief to on-site cables.
Seal any unnecessary apertures with cable grommets
(not cut open).