Configurable inputs
Configurable options
Relay outputs
Number of relay outputs
Relay output specification
Maximum output current
Remote equipment outputs
Output voltage [1]
Minimum
Maximum
Maximum output current
[1] For all local and remote expansion equipment outputs combined.
Mechanical and environmental specifications
Mechanical
Cabinet dimensions (L x W x H)
Weight
Number of cable knockouts
IP rating
Environmental
Operating temperature
Storage temperature
Relative humidity
16
For configuraton options, see your fire panel installation manual.
2
Potential free, NO/NC/C
2 A / 30 VDC
Supply voltage (VIN1, VIN2) − 1.5 V (for example, 22.5 V at 24 V)
Supply voltage (VIN1, VIN2) − 0.6 V (for example, 23.4 V at 24 V)
1A
300 x 61 x 240 mm
2 kg
6 x Ø 20 mm at top of cabinet
4 x Ø 20 mm at bottom of cabinet
6 x Ø 20 mm at back of cabinet
IP30 (DIN rail mounting only)
−5 to +40ºC
−20 to +50ºC
10 to 95% noncondensing