Types Of Operational Parameters; Parameter List - Viessmann FT 0700 Assembly And Operation Manual

Ceiling-mounted refrigeration units
Table of Contents

Advertisement

GB
8.

Types of operational parameters

8.1

Parameter list

Attention!
The following parameters are important for the operation of the refrigeration unit. They may only be changed by
specialists. It is therefore recommended that the password for the access to the parameters be kept secret.
If the parameters are changed, the new ones should be entered in the column „Changed Values".
Parameter for mode of operating (enabling by codeword P01 = 22)
The following parameters are as parameter for mode of operating for cooler resp. freezer prepared.
They can be adjust. If neccessary they can restore through P 50 and P 51 to the factory setting (see 7.5.2.3).
Parameter
P28
Signal Display from DCF Antenna
P29
Door contact switch (0=without/1=with)
Defrosting
x0=according to set cycle times
x1 = according to set cycle times, but dependent on running time
of compressor
P30
x2=dependent on set switch-on times (only with DCF Antenna)
x3=defrosting as required
0y="Defrost Start", door contact switched off
1y="Defrost Start", door contact switched on
P31
Max allowable room temperature
P32
Min allowable room temperature
P33
Room temperature differential
P34
Minimum stop time, compressor
P35
Initiation delay, evaporation fan
P36
Running time after stop, evaporator fan
Running time after stop, evaporator fan, to determine degree
P37
of icing
P38
Temperature difference to allow switch-on of defrosting
P39
Defrost temperature limit
P40
Drainage time, evaporator
P41
Start temperature, evaporator fan
P42
Delay time, temperature alarm
P43
Upper temperature alarm (Setting + P43)
P44
Lower temperature alarm (Setting – P44)
P45
Delay time, door contact alarm
P46
Temperature setting , condenser for rotation speed regulator
P47
Rotation speed, condenser fan in %
P48
Min rotation speed, condenser fan in %
P49
Conductivity, rotation speed regulator, condenser fan
P50
Unit type, 1=normal refrigeration, 2=Deepfreezer
P51
Revert to plant settings (P=78)
General notice (liability): the details of this technical documents serve for description. Consents regarding the availability of certain features or
regarding a certain purpose always require a special written agreement.
Page 16 GB
Description
8 - 8.1
Changed
Unit
Range
values
seconds 0-59
0-1
00-03;
10-13
°C
-50 .. +50
°C
-50 .. +50
K
1-8
minutes 3-10
minutes 0-10
minutes 0-20
minutes 0-10
K
10-40
°C
+5 .. +50
minutes 0-10
°C
-20 .. +10
minutes 0-99
K
0-20
K
0-20
minutes 0-99
°C
0-50
OFF/
10..100
10 .. 100
1-100
1-2
Right reserved to make technical changes!
Recommended
Normal
Deep-
cooling
freezer
0
0
0
0
20
-5
-5
-25
2
2
3
3
3
3
0
0
3
3
25
25
20
20
3
3
-5
-15
60
60
10
10
5
5
4
4
20
20
40
40
10
10
1
2