AEMC GROUNDFLEX 6474 User Manual page 11

Adapter
Hide thumbs Also See for GROUNDFLEX 6474:
Table of Contents

Advertisement

1.
Set the switch of the 6472 to SET-UP.
2. Set the SENSOR TURNS switch to 4.
3. Set the SENSITIVITY switch to x1.
4. Set the INPUT SELECTION switch to 1.
5. Press the Hz/OPTIONS button 5 times.
The device starts by comparing the current I
calibration loop to the current I
are different, the "CAL" symbol blinks to recommend a calibration.
NOTE: To avoid measurement errors, do not touch the GroundFlex
the calibration loop during the calibration.
6. To start the calibration, press 2nd + START.