LG Multi V Series Installation Manual page 24

Indoor unit
Hide thumbs Also See for Multi V Series:
Table of Contents

Advertisement

How to Set E.S.P?
M3 (28k~54k)
Setting
Value
4(39)
6(59)
70
25.2(891)
75
30.4(1 074) 21.4(756)
80
35.0(1 235) 27.1(959)
85
39.8(1 404) 35.4(1 250) 24.6(869)
90
44.3(1 562) 40.1(1 416) 31.5(1 111) 22.7(800)
95
49.3(1 741) 44.8(1 581) 36.8(1 300) 28.8(1 017) 21.4(754)
100
53.0(1 872) 49.4(1 744) 44.6(1 574) 35.4(1 251) 27.7(978)
105
57.2(2 020) 54.1(1 910) 49.2(1 737) 43.0(1 518) 35.0(1 234) 26.5(935)
110
58.8(2 076) 53.9(1 903) 47.9(1 691) 42.4(1 497) 33.8(1 193) 24.3(858)
115
120
125
130
135
Note: 1. The above table shows the correlation between the air rates and E.S.P.
2. Make sure to check and adjust E.S.P (external static pressure) value after the
installation of the product. Otherwise, there is a risk of weak cooling/heating and
condensed water discharge/drop.
24
Indoor Unit
Static Pressure (mmAq(Pa))
8(78)
10(98)
12(118)
18.5(654)
58.6(2 069) 52.9(1 867) 47.8(1 687) 42.5(1 500) 31.4(1 108) 20.3(717)
57.8(2 040) 53.1(1 874) 48.2(1 701) 39.2(1 384) 30.2(1 066) 24.6(868)
54.2(1 913) 49.4(1 744) 43.1(1 520) 36.7(1 296) 33.1(1 168)
54.6(1 927) 52.7(1 860) 48.6(1 714) 44.4(1 567) 39.6(1 398)
(Unit: CMM(CFM))
14(137)
16(157)
18(177)
14.8(522)
50.2(1 772) 45.2(1 596)
20(196)
18.3(646)