Siemens SIPROTEC 4 7XT7100-0 A00/EE Series Product Information page 35

Injection unit (for rotor ground fault protection, 1 hz to 3 hz)
Table of Contents

Advertisement

Available languages

Available languages

12.2 Test Data
12.2.1 Electrical Tests
Standards
Standards:
Installation Requirements
Overvoltage category
Degree of pollution
Protection class
Insulation Test and Safety Test
Standards:
High voltage test (routine test)
Output: Terminals 1, 2 against
all others terminals
High voltage test (routine test)
Auxiliary voltage: Terminals 17, 18,
case against all others terminals
High voltage test (routine test)
Outputs: Terminals 7 to 14 against all
others terminals
Impulse voltage test (type test),
output and auxiliary voltage, class III
SIPROTEC 4/5, Injection Unit 7XT71, Product Information
C53000-B1174-C128-7, Edition 09.2016
IEC 60255-26 (product standard)
IEEE Std C37.90
For more standards see also individual
functions
III
2
1
IEC 60255-27
DC 5.8 kV
DC 3.5 kV
DC 2.5 kV
6 kV (peak);
1.2 µs/50 µs; 0.5 J;
3 positive and 3 negative impulses at inter-
vals of 5 s