Assembly Instructions for SIMATIC NET PROFIBUS SpliTConnect System
Fitting the SpliTConnect M12 outlet
1. Screw the SpliTConnect M12 Outlet (11) onto a
free cable outlet of a SpliTConnect tap (1).
Caution! The contacting element (2) must first be
removed
2. Screw the contacting element (2) onto the
completely assembled SpliTConnect tap (1).
Fitting the SpliTConnect terminator or terminator Ex
1. Insert the SpliTConnect terminator Ex (12) in the
SpliTConnect tap (1).
The alignment is decided by the groove (N) and
the guide on the SpliTConnect terminator Ex (12).
Caution! All 3 outlets must be correctly
assembled.
2. Tighten the SpliTConnect terminator Ex (12) as
far as it will go.
It may help to insert a screwdriver through the
opening in the SpliTConnect terminator Ex (12).
SpliTConnect terminator Ex
ATEX identifier : Ex II 1G Ex ia IIC T6 Ga
Characteristics (terminator Ex)
For connection to an intrinsically safe circuit with degree of protection Ex ia IIC with the following maximum
values:
Maximum output voltage (U
o
Maximum output current (I
)
o
Maximum output power (P
)
o
Ambient temperature (T
)
a
Standards (terminator Ex)
EN 60079-0:2009
EN 60079-11:2007
EN 60079-26:2007
EN 60079-28:2008
A5E03375783A-02
(6GK1905-0AD00)
)
24 VDC
380 mA
5.32 W
-20 °C to +50 °C
General requirements
Intrinsic safety
Device group II, category 1G
Concept for intrinsically safe fieldbus systems (FISCO)
15