Installation with multi-link firmware
Table of Contents

Advertisement

Refer to Figure 3 & Figure 4 and connect the wires from Infinity-controlled devices as follows:
Relay/door 1 .....TB 9
Relay/door 2 .....TB 10
Relay 3 .............TB 11
Relay 4 .............TB 12
Which terminals are used depends on the type of device being controlled:
♦ Dry Contact Closures (most gate operators): Connect wires to NO and COMMON terminals.
♦ Normally Locked Strikes: Connect one wire from the strike power supply to the NO terminal
and one wire from the door strike to COMMON on the same terminal block. Connect the
remaining wires from each source off the board with a wire nut.
♦ Magnetic Locks and Normally Unlocked Strikes: Connect one wire from the power supply
to the NC terminal and one wire from the door strike to COMMON on the same terminal block.
Connect the remaining wires from each source off the board with a wire nut.
Magnetic locks and DC powered strikes produce potentially damaging voltage spikes. Sentex
strongly recommends installing an IN4001 diode across the magnetic lock coil with the cathode
(the banded end) connected to the positive side of the coil, and the anode connected to the
negative side of the coil.
C. OPTIONAL CLOSED CIRCUIT TELEVISION CONNECTIONS
NOTE: You will need a monitor, or a television with a video input to see the picture provided by the
Closed-Circuit Television.
1. Connect a two-conductor 10 to 18 AWG cable (Belden Datalene #9501 or equivalent) to TB1 on the
right lower corner of the CCTV Power Supply Board.
2. Connect coaxial cable (Belden #9240 or equiv.) with BNC connectors (Amphenol #31-71008 or
equiv.) to right angle BNC connector at J2, on the middle bottom of the CCTV Power Supply Board.
Page 8 of 31
CAUTION

Figure 5: Optional CCTV Unit

Doc 6001565