Set Combustion With Test Instruments - Beckett NX Series Manual

Table of Contents

Advertisement

Set Combustion using Test Instruments
NOTICE
The NX burner has a reduced diameter air tube, preci-
sion-designed air throttle cup and combustion head for
improved performance. This design provides very accu-
rate control of the air/fuel ratio, but the light reaching the
cad cell through small holes in these components is lim-
ited. Because of this, the average cad cell resistance
may be higher than conventional burners with larger
openings.
2.
Set the stack or over-fi re draft to the level speci-
fi ed by the appliance manufacturer.
Natural Draft Applications; typically over-fi re
draft is -0.01" or -0.02" w.c.
Direct Venting; typically may not require draft
adjustment.
High Effi ciency/Positive Pressure Appli-
ances; also vary from traditional appliances (see
manufacturer's recommendations).
3.
Follow these fi ve steps to properly adjust the
burner:
Step 1: Adjust the head/air until a trace of smoke
is achieved. This can be accomplished by turn-
ing the screw on the head/air adjustment plate
assembly to increase air (CCW) or decrease air
(CW).
Step 2: At the trace of smoke level, measure the
CO 2 (or O 2 ) . This is the vital reference point
for further adjustments. Example: 13.5% CO 2
(2.6% O 2 )
Figure 10. – Nozzle Line/Head/Air Tube Assembly
RWB 6104 WMNX
Retention Head
Retention Head
Head Support Legs
Head Support Legs
Electrode Tips
Electrode Tips
Nozzle Adapter
Nozzle Adapter
Nozzle
Nozzle
Stops in Retention Ring
Stops in Retention Ring
Retention Ring
Retention Ring
Step 3: Increase the air to reduce the CO 2 by 1.5
to 2 percentage points. (O 2 will be increased
by approximately 2.0 to 2.7 percentage points.)
Example: Reduce CO 2 from 13.5% to 11.5%
(2.6% to 5.3% O 2 ).
Step 4: Recheck smoke level. It should be Zero.
This procedure provides a margin of
reserve air to accommodate variable
conditions.
If the draft level has changed, recheck the
smoke and CO 2 levels and readjust
burner, if necessary.
Step 5: Once the combustion has been set,
tighten the lower acorn nut and splined nut on
the air adjustment assembly. See Figure 9.
4.
Chimney Vent Systems: Install the burner cover
and repeat Steps 2 and 4 above. If CO 2 increas-
es (O 2 decreases), remove the cover and adjust
the air setting so the CO 2 (O 2 ) with the cover
installed meets the requirements of Step 3.
5.
Direct Vent Systems with outside air ducted to
burner: Install the burner cover.
6.
Start and stop the burner several times to
ensure satisfactory operation. Test the primary
control and all other appliance safety controls to
verify that they function according to the manu-
facturer's specifi cations.
(Low fi ring rate shown.)
Electrode Clamp
Electrode Clamp
Electrode Bracket
Electrode Bracket
Electrode Insulator
Electrode Insulator
Bulkhead Fitting
Bulkhead Fitting
Throttle Cup
Throttle Cup
Nozzle Line
Nozzle Line
Throttle Ring
Throttle Ring
Throttle Cup Hub
Throttle Cup Hub
Electrode Extension Rods
Electrode Extension Rods
SK9666A
SK9666A
SK9666A
Page 13

Advertisement

Table of Contents
loading

Table of Contents