5.4 Electrical Installation-Terminals

Power IN For PV-direct systems, a two-pole discon-
nect switch may be installed between the solar array
and the controller. Switch it off to prevent shock and arc
burn hazard during installation and maintenance, or if
the system will be shut down for the season. For
battery systems a 30 Amp slow blow fuse must be
installed between the controller and the battery.
Ground Connect the ground wire to the ground
connection in the controller. Grounding helps to prevent
shock hazard if there is a fault in the motor.
L1 – L2 – L3 ECDRIVE
®
wire) cable between the controller and the motor. The
three wires L1, L2 and L3 carry power. The fourth wire
carries ground. To reverse direction of rotation reverse
any two wires.
No. 1 and 2 In order to protect a pump from being
damaged by dry running connect one well probe cable

5.5 Monitoring

-
+
+
Battery or
Solar for
Solar Direct
Battery Charging
50 V max.
SYSTEM
Green light indicates "SYSTEM ON"
PUMP ON
Green: "MOTOR / PUMP ON"
Red: Motor OFF caused by overload protection
PUMP SPEED
PUMP ON LED will flash in following sequence:
>
300 RPM PUMP ON LED IS ON
>
500 RPM 1 Flash
>
750 RPM 2 Flash
> 1,000 RPM 3 Flash
> 1,250 RPM 4 Flash
> 1,500 RPM 5 Flash
6
requires four-conductor (four-
remote
float switch
-
to each terminal. If dry run protection is not needed,
short cut these two terminals.
No. 3, 4 and 5 Connect any kind of external switch (NO
or NC type) for remote control of the controller. In case
no switch is used the terminals No. 4 and 5 have to be
connected with a short cable (factory setting). In case a
NO-switch is used (connected to the terminals No. 3
and 4) the short cable (connecting the terminals No. 4
and 5) must remain installed.
No. 6 and 7 Connect these two terminals to switch the
controller to battery mode. The motor will be switched
OFF by the controller if the input voltage is below 11 V
for a 12 V battery system and 22 V for a 24 V battery
system in order to protect the battery. If the battery
voltage increases to 13 or 26 V the motor will be
switched ON automatically.
LEDs for Monitoring
RPM
SYSTEM
PUMP ON
OVERLOAD
WELL DRY
TANK FULL/FLASH BATT LOW
BATTERY VOLTAGE
SOURCE LOW
Red light: Water level is low. After recovering the motor
will start within 20 minutes.
Red light will remain ON to indicate low water level has
occurred. For "Reset" press the ON/OFF switch.
TANK FULL
Red light: The motor has been switched OFF by
remote switch.
BATTERY LOW
Red light flashing: "LOW VOLTAGE DISCONNECT"
when battery is empty (in battery mode only)
L
L
L
1
2
3