Download Print this page
Johnson Controls M9206-DN Series Installation Instructions
Johnson Controls M9206-DN Series Installation Instructions

Johnson Controls M9206-DN Series Installation Instructions

Electric spring return economizer damper actuators

Advertisement

Quick Links

M9206-DNx Series Electric Spring Return
Installation
IMPORTANT:
Use this M9206-DNx Series
actuator only to control equipment under normal
operating conditions. Where failure or malfunction of
the damper actuator could lead to personal injury or
property damage to the controlled equipment or
other property, additional precautions must be
designed into the control system. Incorporate and
maintain other devices, such as supervisory or alarm
systems or safety or limit controls, intended to warn
of or protect against failure or malfunction of the
damper actuator.
IMPORTANT :
Utiliser ce M9206-DNx Series
actuator uniquement pour commander des
équipements dans des conditions normales de
fonctionnement. Lorsqu'une défaillance ou un
dysfonctionnement du damper actuator risque de
provoquer des blessures ou d'endommager
l'équipement contrôlé ou un autre équipement, la
conception du système de contrôle doit intégrer des
dispositifs de protection supplémentaires. Veiller
dans ce cas à intégrer de façon permanente d'autres
dispositifs, tels que des systèmes de supervision ou
d'alarme, ou des dispositifs de sécurité ou de
limitation, ayant une fonction d'avertissement ou de
protection en cas de défaillance ou de
dysfonctionnement du damper actuator.
The M9206-DNx actuator is designed for use with the
Johnson Controls AD-DME100-0 Economizer
Controller.
Parts Included
The M9206-DNx actuator is included.
Special Tools Required
5/16 in. (8 mm) square socket or 3/8 in. (10 mm)
12-point socket
5/16 in. (8 mm) hex socket or nut driver
© 2014 Johnson Controls, Inc.
Part No. 34-1280-130, Rev. C
Economizer Damper Actuators
Installation Instructions M9206-DNx
Setup and Adjustments
Spring Return Direction - Counterclockwise (CCW)
Operation
For CCW spring return operation, mount the actuator
to the damper shaft so the CCW face of the actuator
(Figure 1) is away from the damper. The coupler is at
the 0° position to drive Clockwise (CW) and spring
return CCW.
0° Position
Auxiliary
Switch
Adjuster
Located
on the Left
Figure 1: CCW Face of the Actuator
Spring Return Direction - Clockwise (CW)
Operation
To change the spring return direction to CW, mount
the actuator to the damper shaft so the CW face of the
actuator (Figure 2) is away from the damper. The
actuator now drives CCW from the 0° position.
Arrow
Indicating
CW
Spring Return
Direction
Figure 2: CW Face of the Actuator
Issue Date August 29, 2014
Arrow
Indicating
CCW
Spring Return
Direction
0° Position
Auxiliary
Switch
Adjuster
Located
on the Right
www.johnsoncontrols.com
1

Advertisement

loading
Need help?

Need help?

Do you have a question about the M9206-DN Series and is the answer not in the manual?

Questions and answers

Summary of Contents for Johnson Controls M9206-DN Series

  • Page 1 5/16 in. (8 mm) square socket or 3/8 in. (10 mm) on the Right 12-point socket • 5/16 in. (8 mm) hex socket or nut driver Figure 2: CW Face of the Actuator © 2014 Johnson Controls, Inc. Part No. 34-1280-130, Rev. C www.johnsoncontrols.com...
  • Page 2 Insert the coupler in the CW face of the actuator for Mounting easier access to the coupler set screw. (Refer to the Mount the M9206-DNx actuators in any convenient Removable Coupler section.) orientation in economizer applications only. Install the actuators on a 1/2 in. (13 mm) round damper shaft, Removable Coupler using the M9000-159 anti-rotation bracket.
  • Page 3 4. Rotate the damper to the desired position when 3. Snap the locking clip securely into the coupler power is lost. If a tight seal is required, grasp the groove to retain the coupler in the actuator. damper drive shaft with pliers and compress the damper seals.
  • Page 4: Repairs And Replacement

    The switch point is continuously adjustable from 0 to 90°. For the most accurate position of the switch, CAUTION: Risk of Property Damage. refer to Figure 9 and use the method in the following Do not plug or unplug an actuator into a DME example.
  • Page 5: Technical Specifications

    The performance specifications are nominal and conform to acceptable industry standards. For application at conditions beyond these specifications, consult the local Johnson Controls office. Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or misuse of its products.