Wiring Diagrams; Control Tc Plus - Ferroli JOLLY Plus 2 VERSIONE VM-F Installation Manual

Tangential fan coil units with brushless motos
Hide thumbs Also See for JOLLY Plus 2 VERSIONE VM-F:
Table of Contents

Advertisement

Available languages

Available languages

For all units with remote interface
Before closing the electrical box remember to carry out the connection to the remote interface according to the
specific instructions supplied .

Control TC PLUS

Control TC PLUS
H2*
water temperature probe 10 kΩ
AIR
air temperature probe 10 kΩ
M1
fan motor DC inverter
S1
grill safety micro-switch
water solenoid valve (230V/50Hz 1A powered
Y1
output)
L-N
230V/50Hz electrical power supply connection
22
6

WIRING DIAGRAMS

INSTALLATION
BO
CH
CP
*
boiler go-ahead output (free contact max 1A)
chiller go-ahead output (free contact max 1A)
presence sensor input (if closed, the fan coil
goes into stand-by .)
If after powering the equipment the board
detects the probe, the start-up will take
place under normal conditions with minimum
water temperature in heating (30 °C) and
maximum water temperature in cooling (20
°C) functions .
The board can also operate without probe,
case in which the minimum and maximum
thresholds will be ignored .
Fig .1

Advertisement

Chapters

Table of Contents
loading

This manual is also suitable for:

Jolly plus 2 versione vn

Table of Contents