The mounting plate should be installed on a wall which can
support the weight of the indoor unit.
(1.) Temporarily secure the mounting plate to the wall, ensure
the panel is completely level, and mark the boring points
on the wall.
(2.) Secure the mounting plate to the wall with screws.
6screws
Fig. 74 – Floor Installation
6screws
Fig. 75 – Wall Installation
Cut exactly
Renove
at right
burrs
angles
Casing
Molding
Flaring
Set exactly at the position shown below
Flare tool for R410A
A
Clutch-type
Die
A
0~0.02 in (0~0.5 mm)
Fig. 76 – Flaring
(3.) Once refrigerant piping and drain piping connections are
complete, fill in the gap of the through hole with putty.
A gap can lead to condensation on the refrigerant pipe,
and drain pipe, and the entry of insects into the pipes.
(4.) Attach the front panel and front grille in their original
positions once all connections are complete.
Flaring the Pipe End
1 Cut the pipe end with a pipe cutter.
2 Remove burrs with the cut surface facing downward so that
the chips do not enter the pipe.
3 Fit the flare nut on the pipe.
4 Flare the pipe.
5 Check that the flaring is properly made.
!
WARNING
(1.) DO NOT use mineral oil on the flared part.
(2.) Prevent mineral oil from getting into the system as
this would reduce the lifetime of the units.
(3.) Never use piping which had been used for
previous installations. Only use parts which are
delivered with the unit.
(4.) Do never install a drier to this R410A unit to
guarantee its lifetime.
(5.) The drying material may dissolve and damage the
system.
(6.) Incomplete flaring may cause refrigerant gas
leakage.
Wireless Remote Controller Installation
Mounting Bracket (if installed on the wall)
1 Use the two screws supplied with the controller to attach the
Mounting Bracket to the wall in a location selected by the
customer and within operating range.
2 Install the batteries in the Remote Controller.
3 Place the Remote Controller in the remote control Mounting
Bracket.
NOTE: For remote controller operation, refer to the unit Owner's
Manual.
Wired Remote Controller (Not Available)
Flare's inner
surface must
be scratch-free
Conventional flare tool
Clutch-type
Wing-nut type
(lmperial-type)
(Rigid-type)
0.04~0.06 in
0.06~0.08 in
(1.0~1.5 mm)
(1.5~2.0 mm)
37
The pipe end must
be evenly flared in
a perfect circle
Make sure that the
flare nut is fitted

Hide quick links: