Honeywell MPD Series Operating Manual page 29

Table of Contents

Advertisement

94 MPD-IV1
Characteristic
Gases Detected: Methane gas in the %Vol and %LEL range.
Measuring Range: 0 – 5.00%Vol
Operating Temperature Range: -20°C to +50°C
Operating Humidity Range: 0 to 95% RH non-condensing
Operating Pressure Range: 80 to 110 kPa
Warm Up Time: 3 minutes
Response Time: T90 = <30 seconds
Voltage Range: 3.0V ~ 5.0V (From control equipment)
Drive Current: 75mA ~ 85mA (From control equipment)
Power Consumption: <500mW
Signal Output: mV Bridge
Zero Stability with Time: <±3% FS/year
Span Stability with Time: <±5% FS/year
Span Stability with
Expected Operating Life: 5 years
MPD Operating Manual
0 – 100%LEL
Time to reach 90% of a step change in gas concentration of
100% of FS Methane
Linearity: <±5% FS
Accuracy: <±5% FS
<±10% of reading up to 50% FSD, ±15% of reading from
Temperature:
50% to 100% FSD or 2% FSD whichever is greater over the
operating temperature range.
Dimensions: 2.080 in Dia x 3.016 in L / 52.83 mm Dia x 76.62 mm L
Weight: 1.2 lbs / 544.3g
Description