Fitting Accessories 16; 31 Collecting Cone 16; 35 Duct Mount Kit 16 - Honeywell MPD Series Operating Manual

Table of Contents

Advertisement

3 Fitting Accessories
31 Collecting Cone
(02000-A-1462)
To fit the Collecting Cone to a sensor, carry out the following:
1. Remove the Filter Housing and gasket from the sensor.
2. Fit the Stainless Steel Filter.
3. Screw the Collecting Cone onto the sensor accessory thread and
tighten firmly by hand.
See Appendix A in the XNX Technical Manual for more Local HART Handheld.
information.
32 Weatherproof Housing
(SPXCDWP)
For FM 6340 performance approvals on MPD-BT-IC1 and MPD-UT-IC1,
SPXCDWP must be installed for IP66 compliance.
Note: Environmental conditions that compromise the IP66 protection
provided by the weather proof cover will extend published response
times. Safety protocols or maintenance procedures that consider these
environmental conditions are recommended specific to the installation.
33 Weatherproof Cap
(02000A1640)
To fit a Weatherproof Cap to a sensor carry out the following:
1. Remove the Filter Housing and gasket from the sensor.
2. Fit the Stainless Steel Filter.
3. Screw the Weatherproof Cap on to sensor accessory thread and
tighten firmly by hand.
34 Sample/Calibration Gas Flow Adaptor
(1226A0411)
To fit a Flow Adaptor to the sensor, carry out the following:
1. Remove the Filter Housing and gasket from the sensor.
2. Ensure that the Flow Adaptor is fitted with its gasket.
3. Apply a thin coating of anti-seize compound, such as light petroleum
grease, to the sensor accessory thread.
4. If required fit the Stainless Steel Filter, screw the Flow Adaptor on
to the sensor and tighten with a 47mm A/F spanner.
5. Set the sample flow rate to 0.5 ± 0.2 liters per minute, unless
otherwise directed in System installation instructions.
See Appendix B in the XNX Technical Manual for more Modbus. information.
35 Duct Mount Kit
The Duct Mounting Kit (S3KDMK), when combined with the MPD
Interface Adaptor (1226A0382), the Duct Mounting Kit can
accommodate the MPD to detect flammable gases in a duct application.
The kit includes the adaptor, gasket and required fasteners. The MPD
Interface Adaptor includes only the adaptor and requires the S3KDMK
Duct Mounting Kit.