Install Differential Pressure Sensor: Mounting Kit For Through The Wall Install; Typical Installation Illustration; Supplied Components - OneVue A120 Installation Manual

Sense differential pressure sensor
Table of Contents

Advertisement

Install Differential Pressure Sensor: Mounting kit for through the wall
install
A Differential Pressure Sensor mounting kit is used for through-the-wall installation in combination with a Differential
Pressure Sensor. The kit allows assembly through either a solid or hollow wall.

Typical installation illustration

Add: sensor with tube attached to H pressure port if in sensor in Reference Space. Sensor installed in Controlled
Space and tube attached to L pressure port.

Supplied components

Quantity
Component
1
Sensor device
1
Removable port cover
2
Flexible silicone tube measuring 6 feet (1.82 m), 1/8 in. (3.17 mm) inner diameter (I.D.), 1/4 in. (6.3 5 mm) outer diameter (O.D)
1
AC power supply: 5V DC USB Mini B (5 pin) connector interface, 5 ft (1.5 m) cable, Input: 100-240 VAC, 50/60 Hz, 0.4A, Output: 5V DC, 1.0A
max
1
Primex 3.0v Lithium/Iron Disulfide Battery Pack (contains 2 AA 1.5V Energizer® Ultimate Lithium batteries). Estimated battery life: Up to
18 months with use of Lithium 1.5V batteries; estimation based on 1 hour Logging Interval, 8 hour Check-In Interval, and adequate wireless
signal
4
3M™ Dual Lock™ Tape, 2 in. x 1 in. strips
1
USB configuration cable; one cable is supplied with a device order only. For use with the Primex Device Configuration software to manually
configure a device or troubleshoot device network connectivity issues. It's recommended to save this cable for future use.