Sensor Led Indicators; Sensor Audio Alert - OneVue A120 Installation Manual

Sense differential pressure sensor
Table of Contents

Advertisement

Button
Operation
Check-
Pressing and releasing the check-in
in button
readings are transmitted to OneVue and any pending updates are downloaded to the device. During an active check-in connection,
additional pressing of the check-in button is ignored.
When the check-in button is pressed and released, the device emits a series of audio beeps indicating its connection sequence. When a
device emits beeps as indicated below and displays Signal Ok, this indicates a successful check-in.
• 1 beep: device booted
• 2 beeps: device connected to network
• 3 beeps: device connected to OneVue
If a check-in fails, commonly due to the device cannot establish a network connection, all logged readings are stored in the device's non-
volatile memory. If the number of failed check-ins exceeds the size of the non-volatile memory, the oldest readings are overwritten.
Primex sensor devices store up to 4096 readings.

Sensor LED indicators

Primex sensors have three LED indicators that provide a visual indicator of its current state.
When power is first applied, the LCD segments display and LED indicators briefly illuminate.
LED
State/Status
Green LED illuminated
Normal state
Operating as expected
Yellow LED flashing
Warning state
• Low battery
• Unresponsive
Alarm state
• No Temp Probe or Water Detector
Red LED flashing
Reading Alarm
• Out of Range, Past Alarm Delay

Sensor audio alert

Primex sensors are equipped with an audio alert that is activated during a reading Alarm state (Out of Range, Past
Alarm Delay status). The audio alert is activated when a reading is out of range and the time period it has been out of
range has exceeded the time period set in its Alarm Delay.
• When the audio alert is enabled and the sensor is in a reading alarm state, the device emits an audio beep at one
second intervals. Also, when powered by AC or PoE, the sensor's red LED flashes once per second.
• During a reading Alarm state, pressing and immediately releasing the silence button
stops the red LED from flashing, but does not acknowledge the alert in your OneVue account. The audio alert
resumes once the time period of the Resume Audio Alert setting has been reached. Audio alert settings are
configured from a sensor's gateway profile.
button during normal operation initiates a check-in to OneVue. During a check-in, all logged
Device power
AC or PoE power: LED illuminated
Battery-power only: LED disabled to conserve battery life. Upon power up,
illuminates for 2 seconds
AC or PoE power: LED illuminated and flashes
Refer to the LCD display to identify the condition
All power methods: LED illuminated and flashing
clears the audio alert and