Huawei NetCol5000-A021HN12D 20020E1 Quick Manual page 4

In-row air cooled smart cooling product
Table of Contents

Advertisement

2.3
Copper Pipes
Gas pipe
3/4 inch (19.05 mm)
1.0 mm for liquid pipes wall thickness, 1.0 mm for gas pipes wall thickness; operating pressure:
≥ 4.5 MPa.
Thermal insulation foam: thickness ≥ 13 mm.
2.4
Oil Traps and Inverted Traps (unit: mm)
Oil trap
Pipe Supports
2.5
1. Height of the U-shaped clamp H = Pipe diameter (with thermal insulation foam) – 5 mm.
2. The material for pipe supports and clamps should meet outdoor application requirements.
3. When the pipe is straight, add a support every 1500 mm. When the direction of the pipe is
changed, add a support at the position that is 500 mm away from the changing point.
Pipe support
Bases
2.6
For the outdoor concrete base dimensions, see chapter 4.
Liquid pipe
5/8 inch (15.88 mm)
Gas pipe inverted trap
3
Liquid pipe inverted
trap