On the main screen, tap Settings > System Settings > T/H Sensor to change temperature and
humidity control types or set points.
(Optional) Operation Guide for Teamwork Connection
12.4
The networking mode can be MAC_CAN networking or CAN networking. The default
networking mode is MAC_CAN networking, that is, FE teamwork networking.
The networking mode set on the screen must be consistent with the actual networking mode.
Otherwise, the teamwork control function will be unavailable. If the networking mode changes,
select the corresponding networking mode on the screen. If the networking mode is changed
on the screen, the software will restart and then run in the new networking mode.
On the home screen, tap
Teamwork Settings. Set Network as follows.
NOTE
User name: Admin. Preset password:
000001. For system security purposes,
change the preset password upon first login.
Using 32 smart cooling products in
teamwork as an example:
No.
Teamwork
group no.
1
1
2
1
3
1
......
......
31
1
32
1
13
Commissioning
Before starting the compressor, ensure that the crankcase heat tape has worked for over 12
hours. Otherwise, no maintenance operation is allowed.
If electric heater, humidifier and water pump are not configured, skip the commissioning
procedures for the electric heater, humidifier and water pump.
1. Turn on the output power breaker QF3 that controls the compressor and outdoor unit and the QF4
circuit switch that controls the heater and humidifier.
2. Check that the power indicators of the PSU, auxiliary power supply module, and main control
modules are on.
3. Tap Start and choose Maint > Diagnostic Mode > Enter. (If no manual operation is performed
within 25s after you tap Start, the equipment will automatically run following the preset logic, and
the compressor and indoor and outdoor fans will also run according to the environment.)
>
Teamwork
Teamwork
unit
function
address
1
2
3
Enable
......
31
32
Item
Network
Networked over
CAN or
MAC_CAN.
23
Total
Number of
number of
running units
units
32
30 (2 standby)
/
/
......
......
/
/
/
/
/
/