Bosch FLM-420-I2-E Installation Manual page 11

Input interface module type in-built
Hide thumbs Also See for FLM-420-I2-E:

Advertisement

Available languages
  • EN

Available languages

  • ENGLISH, page 11
11
en
Safety Notes
NOTICE!
Installation must only be performed by authorized and specialized personnel.
CAUTION!
Electrostatic discharge (ESD)! Electronic components could become damaged.
Ground yourself using a wrist strap or take other suitable actions.
Functional description
FLM-420-I2 Input Interface Modules provide three monitoring functions:
-
Monitoring a line with EOL resistor for standby or triggering (interruption/short circuit)
-
Monitoring a potential free contact for "open" and "closed" states
-
Voltage monitoring between 0 and 30 V DC.
The FLM-420-I2-E type in-built can be flush mounted in standard device boxes in accordance with EN 60670 (e.g. in
standard switching programs); alternatively, it can be installed in the devices (see Figure 8, Page 6 to Figure 10,
Page 7).
Address Setting
Address setting is carried out using the 8 DIP switches and a suitable pointed object (see Figure 1, Page 3 to
Figure 6, Page 5).
Address (A) Operating mode
0
Loop/stub in LSN improved version mode with automatic addressing
1 - 254
Loop/stub/T-taps in LSN improved version mode with manual addressing
255 = CL
Loop/stub in LSN classic mode (address range 127 max.)
Connection
See Figure 7, Page 6.
Description
LSN: a1- | b1+ | a2- | b2+
LSN-POWER: 0 V | 0V | +24V | +24V LSN power supply (support points to loop through)
LSN-SHIELD
IN: IN1+ | IN1- | IN2+ | IN2-
Technical specifications
Inputs
LSN input voltage
Max. current consumption from LSN
Contact monitoring:
-
EOL resistor
-
Max. current strength (current pulse)
-
Total resistance of the line
Voltage monitoring:
-
Voltage range
-
Input resistance
-
Number of selectable threshold values
Permissible wire diameter
Cable length per input
Permissible operating temperature/storage temperature
Permissible rel. humidity
Protection class as per IEC 60529
Classes of equipment as per IEC 60950
Housing material and color
Dimensions (Ø x H)
F.01U.012.987 | 6.0 | 2011.01
Function
LSN b incoming / LSN b outgoing
Cable shielding (if present)
Input 1 / Input 2
2, independent
15 to 33 V DC
10.4 mA
Nominal, 3.9 kΩ
8 mA
In standby: 1500 Ω to 6000 Ω
Short-circuit: < 800 Ω
Interruption: > 12000 Ω
0 to 30 V DC
> 50 kΩ
4 (see programming software)
2
0.6 to 2.0 mm
Max. 3 m
-20 °C to +65 °C / -25 °C to +80 °C
<96 %, non-condensing
IP 30
Class III equipment
ABS + PC-Blend, signal white (RAL 9003)
Approx. 50 mm x 22 mm
FLM-420-I2-E
Bosch Sicherheitssysteme GmbH