Introduction General description This manual contains information for the installation and operation of the PM4-BC Monitor. The PM4 is a general purpose instrument which may be configured to accept inputs of: Binary (SEt INPt function set to bin) 5.27 BCD (SEt INPt function set to bcd) 5.27...
Mechanical Installation Choose a mounting position as far away as possible from sources of electrical noise such as motors, generators, fluorescent lights, high voltage cables/bus bars etc. An IP65 or IP67 access cover which may be installed on the panel and surrounds is available as an option to be used when mounting the instrument in damp/dusty positions.
Electrical installation Electrical installation The PM4 Panel Meter is designed for continuous operation and no power switch is fitted to the unit. It is recommended that an external switch and fuse be provided to allow the unit to be removed for servicing. The plug in, screw type, terminal blocks allow for power supply wires of up to 2.5mm to be fitted.
Page 6
Instrument label (example) Resistor pack and link locations Electrical connection examples 6 of PM4BCMAN-2.0-0...
Page 10
Parallel binary input (also used for Gray code) 10 of PM4BCMAN-2.0-0...
Page 11
Strobed binary input (also used for Gray code) PM4BCMAN-2.0-0 11 of...
Page 12
3.10 Addressed binary input (also used for Gray code) 12 of PM4BCMAN-2.0-0...
Page 13
3.11 Remote decimal point selection and display hold For up to 4 digit parallel BCD or addressed BCD or strobed BCD inputs terminals 18, 19 and 20 may be used to select the decimal point position. To allow these inputs to be used in this manner the dP INPt function must be set to on.
Page 14
3.12 Weighted digital input See chapter for description of this input type. 14 of PM4BCMAN-2.0-0...
Page 15
3.13 Input Output Configuration If you need to alter the input or output configuration link settings proceed as follows: 1. Remove the plug in terminals from the rear of the instrument 2. Remove the 4 x self tapping screws from the back cover then remove the back cover by pulling it away from the instrument 3.
Function tables - summary of setup functions Note: the order in which the functions appear on the display may not be exactly as shown below. The availability and order of functions is determined by choice of function settings and options fitted.
Page 17
Functions in this second table are available only in CAL mode or if ACCS is set to ALL Display Function Range Default Your Ref/Page record bAr, S.dot, Bargraph type for instruments 5.13 tYPE d.dot, with bargraph display (seen C.bAR or only on bargraph display r.dot instruments)
Page 18
1 to number of Number of BCD digits to be 5.32 dIGt displayed display digits on the instrument on or OFF Remote decimal point on or off 5.33 INPt INPt on or OFF Remote display hold on or off 5.34 HOLd HOLd Hi or Lo...
Explanation of functions The PM4 setup and calibration functions are configured through a push button sequence. The three push buttons located at the rear of the instrument (also at the front on some display options) are used to alter settings. Two basic access modes are available: FUNC mode (simple push button sequence) allows access to commonly set up functions such as alarm setpoints.
Page 20
Example: Entering FUNC mode to change alarm 1 high function A1Hi from OFF to 100 Press & release Press & release Press & release F U N C A 1 H i O F F F until then press until Press &...
Page 21
Explanation of Functions Alarm relay low setpoint A Lo Display: Any display value or OFF Range: Default Value: OFF Optional relay low setpoint (binary, Gray code, whole number BCD (bcd COdE = 0) and weighted digital inputs only) - note there is no relay 1 therefore relay numbering starts from will be replaced by the relay number when displayed e.g.
Page 22
used the relay will be activated when the display reading moves outside the band set between low and high setpoints. Example: If A2Hi is set to 100 then relay 2 will activate when the display value is 100 or higher. Display Value Relay resets...
Page 23
Alarm relay trip time A tt Display: 0 to 9999 Range: Default Value: 0 Displays and sets the alarm trip time in seconds. The trip time is common for both alarm high and low setpoint values (binary, Gray code, whole number BCD (bcd COdE = 0) and weighted digital inputs only) - note there is no relay 1 therefore relay numbering starts from 2.
Page 24
set the required operation then press F to accept this selection. Example: If set to A2n.o alarm relay 2 will be open circuit when the display is outside alarm condition and will be closed (short circuit across terminals) when the display is in alarm condition. Alarm relay setpoint or trailing operation A3.SP or A3.t2 etc.
Page 25
may scaled differently to the 7 segment display. For example the bargraph scale may be indicating percentage fill of a tank whilst the 7 segment display is indicating actual process units. To set bargraph low level go to the bAr_ function and use the ^ or v push buttons to set the value required then press F to accept this value.
Page 26
5.13 Bargraph type for instruments with bargraph display bAr tYPE Display: bAr, S.dot, d.dot, C.bAR or r.dot Range: Default Value: bAr Bar graph display operation mode - seen only in vertical or circular bargraph display instruments. Allows selection of bargraph operation mode. Choices available are: bAr - conventional solid bargraph display i.e.
Page 27
5.14 Digital output option mode dGOP Display: bcd, b.SCL, bin or bin2 Range: Default Value: bin2 Seen only with the 16 bit digital output option. Refer to the separate “PM4 Panel Meter Optional Output Addendum” booklet supplied when this option is fitted. Selections available are: bin2 (signed binary) i.e.
Page 28
5.18 Digital output option high value diG~ Display: Range: Any display value Default Value: 1000 Seen only with the 16 bit digital output option. Refer to the separate “PM4 Panel Meter Optional Output Addendum” booklet supplied when this option is fitted. Determines the high scaling point for the b.SCL mode and has no effect on other modes.
Page 29
that the valley memory value is being displayed. HiLo - toggle between Hi and Lo displays. This function allows the remote input to be used to toggle between peak and valley memory displays. The first operation of the P button will cause the peak memory value to be displayed, the next operation will give a valley memory display.
Page 30
5.24 Display rate dISP RAtE Display: 1, 2, 4, 8, 16 or 32 Range: Default Value: 4 Display rate - allows selection of display update rate from 1, 2, 4, 8, 16 or 32 updates per second. 5.25 Number of weighted digital input d.inP Display: 1 to 8...
Page 31
5.29 Data polarity dAtA POL Display: Hi or Lo Range: Default Value: Hi Data polarity - Allows selection of active low (Lo) or active high (Hi) data inputs. 5.30 Strobe polarity Strb POL Display: Hi or Lo Range: Default Value: Hi Strobe polarity - Allows selection of active low (Lo) or active high (Hi) strobe inputs.
Page 32
5.33 Remote decimal point on or off dP INPt Display: on or OFF Range: Default Value: OFF Remote decimal point selection - for addressed, strobed or 4 digit parallel BCD inputs only there is a choice of setting the decimal point place either in software via the dCPt function or remotely via rear terminals 18, 19 and 20, see section 3.11.
Page 33
5.37 First scaling point CAL1 Display: Range: Default Value: n/a First scaling point - see “Scaled inputs” chapter for description. 5.38 Second scaling point CAL2 Display: Range: Default Value: n/a Second scaling point - see “Scaled inputs” chapter for description. 5.39 Scaling offset CAL OFSt...
Page 34
5.42 Output mode for optional serial communications O.Put Display: dISP, Cont, POLL, A.buS or M.buS Range: Default Value: Cont Set serial interface mode - seen only with serial output option. Refer to the separate “PM4 Panel Meter Optional Output Addendum” booklet supplied when optional outputs are fitted. Allows user to select the serial interface operation as follows: disP - sends image data from the display without conversion to ASCII.
Scaled inputs This chapter covers the scaled binary/Gray/BCD code facility of the PM4-BC display (note for BCD inputs the bcd COde function must be set to 0 if scaling is required). This facility allows the display value for an input to be scaled by a two point scaling i.e. the display does not need to follow normal binary or Gray code values.
Page 36
5. Press the F button, the message SCL2 will be seen followed by a value. Use the ^ or v button if required to make this value read 3000. 6. Press the F button the message CAL End followed by the next function will be seen. Press and release the F button until the message FUNC End is seen and the display moves back to normal display mode.
3.12 for electrical connection details. This chapter describes the special weighted digital input mode available on the PM4-BC. To operate in this mode the SEt INPt function must be set to d.inP. The weighted digital input mode allows up to 8 inputs to be given weighted values, these weighted values are added together for each active input.
Page 38
The result of these inputs are shown in the table below. Input 1 state Input 2 state Input 3 state Input 4 state Display Retransmission 0.00 Inactive Inactive Inactive Inactive 1.00 Active Inactive Inactive Inactive 3.00 Inactive Active Inactive Inactive 4.00 Active Active...
Specifications Technical specifications Input data: 20 input lines for BCD, binary or Gray code addressed and strobed inputs can be used to give up to 8 digit display or special weighted digital input (up to 8 inputs). For BCD inputs four of the 20 input bits can be assigned for use as remote decimal point and display hold if required.
Physical Characteristics Bezel Size: DIN 48mm x 96mm x 10mm Case Size: 44mm x 91mm x 120mm behind face of panel Panel Cut Out: 45mm x 92mm +1mm/-0mm Connections: Plug in screw terminals (max. 2.5mm wire) Weight: 400 gms basic model, 450 gms with option card Guarantee and service The product supplied with this manual is guaranteed against faulty workmanship for a period of two years from the date of dispatch.