2. Select the configuration option Configuration with Installation Assistant.
☑ The installation assistant will open.
3. Make the network configuration or apply the automatic configuration and select [Save and
next].
4. Set the Automatic time synchronization to [On] and in the drop-down list Time zone
select the desired time zone.
5. Select [Save and next].
6. In the drop-down list Set country standard select the desired country standard and then
[Save and next].
7. In the step Meter configuration, select Wattnode Modbus RTU from the Used energy
meter drop-down list.
8. Select [Save and next].
9. Grid management service configuration:
• From the drop-down list Connected line conductors, select the line conductor to which
the battery inverter is connected.
• Set Feed-in management at the grid-connection point to [Off].
• Select [Save and next].
10. In the step Configuration battery/battery-backup system, check if the connected battery
has been detected and the correct battery type and serial number are listed in the overview
Detected battery types and if a green check mark appears in the overview Status.
11. Select [Save and next].
12. Check all settings in the summary. You can export the summary or all parameters. Once all
settings are correct, select [Next]. The configuration of the Sunny Boy Storage is now
complete.
6.3.4
Setting Time-of-Use (optional)
Time-of-Use
With the "Time-of-Use" function, you can adjust the charging behavior of the battery to your
electricity tariff. Energy bills are thus reduced and electricity at lower cost can be used. You can
determine in which time range the battery with a specified charging power is operated. At specific
times, this is mostly useful when the battery's state of charge has to take on a certain value or the
tariff situation makes the charging more attractive, regardless of the power at the grid-connection
point. The charging parameters set in the power profile are only limited by the state of charge
(SOC). At times when the "Time-of-Use" function is not enabled, the battery is charged
correspondent to the increased self-consumption for the entire system. The "Time-of-Use" function is
disabled by default and must be enabled by creating power profiles.
Procedure:
1. Activate the battery inverter user interface.
2. Log in as Installer.
3. Select the menu User settings.
4. Select [Power profile].
System Manual
6 Commissioning
SBSUL9540-SH-en-10
21