York eco YCAS Series Manual page 213

Optimized r-407c air-cooled liquid chiller
Table of Contents

Advertisement

High Ambient Temperature Cutout
H I G H
A M B I E N T
C U T O U T
=
1 3 0 . 0 ° F
Low Ambient Temperature Cutout
L O W
A M B I E N T
C U T O U T
=
T E M P
T E M P
2 5 . 0 ° F
Operation below 1°F (-17°C) may oc-
casionally cause nuisance low pres-
sure safety shutdowns. This will gen-
erally not cause a problem provided
ambient temperature is not expected
to be below 1°F (-17°C) for more than
a short time.
Low Leaving Liquid Temperature Cutout
L E A V I N G
L I Q U I D
C U T O U T
=
High Motor Current Unload Point
H I G H
M O T O R
U N L O A D
=
1 0 5 %
T E M P
3 6 . 0 ° F
C U R R E N T
F L A
213