York eco YCAS Series Manual page 212

Optimized r-407c air-cooled liquid chiller
Table of Contents

Advertisement

Micro Panel Contents
High Discharge Pressure Unload Point
D I S C H A R G E
U N L O A D
=
3 6 0 . 0
Low Suction Pressure Cutout
S U C T I O N
P R E S S U R E
C U T O U T
=
4 4 . 0
212
P R E S S U R E
P S I G
P S I G
Programmed
X
Cutout
Example: If programmed Cutout = 44 PSIG (3 bar)
and Run Time = 60 seconds
60/3 + 10
New Cutout = 44 X
100
Programmed
100 - transient time remaining
X
Cutout
Example:
If programmed Cutout = 44 PSIG (3 bar)
and the timer has run 30 seconds:
New Cutout = 44 PSIG X 100-60 = 17.6 PSIG (1.2 bar)
Run Time/3 + 10
100
= 13.2 PSIG (0.9 bar)
100
100

Advertisement

Table of Contents
loading