York eco YCAS Series Manual page 198

Optimized r-407c air-cooled liquid chiller
Table of Contents

Advertisement

Micro Panel Contents
for a YCAS 2 System Chiller. YCAS 3 System models
and YCAS 4 System models provide similar printouts
for the appropriate number of systems:
YORK INTERNATIONAL CORPORATION
2
eco
UNIT STATUS
2:04PM 10 OCT 98
SYS 1
NO COOLING LOAD
SYS 2
COMPRESSOR RUNNING
OPTIONS
CHILLED LIQUID
AMBIENT CONTROL
REFRIGERANT TYPE
PROGRAM VALUES
DSCH PRESS CUTOUT
DSCH PRESS UNLOAD
SUCT PRESS CUTOUT
HIGH AMBIENT CUTOUT
LOW AMBIENT CUTOUT
LEAVING LIQUID CUTOUT 36.0 DEGF
MOTOR CURRENT UNLOAD
ANTI RECYCLE TIME
LOCAL/REMOTE MODE
LEAD/LAG CONTROL
UNIT DATA
LEAVING LIQUID TEMP
RETURN LIQUID TEMP
MIXED LIQUID TEMP
COOLING RANGE 42.0 +/- 2.0 DEGF
AMBIENT AIR TEMP
LEAD SYSTEM
EVAPORATOR PUMP
EVAPORATOR HEATER
ACTIVE REMOTE CONTROL
SOFTWARE VERSION
SYSTEM 1 DATA
COMPRESSORS STATUS
RUN TIME
0- 0- 0- 0 D-H-M-S
MOTOR CURRENT
SUCTION PRESSURE
DISCHARGE PRESSURE
OIL PRESSURE
SUCTION TEMPERATURE
DISCHARGE TEMPERATURE 68.8 DEGF
OIL TEMPERATURE
SAT SUCTION TEMP
SUCTION SUPERHEAT
SAT DISCHARGE TEMP
DISCHARGE SUPERHEAT
SLIDE VALVE STEP
COOLER INLET REFRIG
LIQUID LINE SOLENOID
ECONOMIZER TXV SOLENOID
CONDENSER FAN STAGE
COMPRESSOR HEATER
WYE-DELTA RELAY
198
SCREW CHILLER
WATER
STANDARD
R-407C
399 PSIG
375 PSIG
44 PSIG
130.0 DEGF
25.0 DEGF
100 %FLA
600 SECS
REMOTE
AUTOMATIC
49.0 DEGF
58.2 DEGF
51.3 DEGF
74.8 DEGF
SYS 2
ON
OFF
NONE
C.ACS.09.00
OFF
0 AMPS
0 %FLA
125 PSIG
131 PSIG
130 PSIG
68.4 DEGF
68.8 DEGF
71.8 DEGF
3.4 DEGF
74.5 DEGF
6.3 DEGF
0
44.6 DEGF
OFF
OFF
OFF
ON
OFF
FORM 201.18-NM9 (602)
SYSTEM 2 DATA
COMPRESSORS STATUS
RUN TIME
0- 0-15-26 D-H-M-S
MOTOR CURRENT 104 AMPS 87 %FLA
SUCTION PRESSURE
57 PSIG
DISCHARGE PRESSURE
233 PSIG
OIL PRESSURE
218 PSIG
SUCTION TEMPERATURE
42.9 DEGF
DISCHARGE TEMPERATURE 145.5 DEGF
OIL TEMPERATURE
102.8 DEGF
SAT SUCTION TEMP
31.7 DEGF
SUCTION SUPERHEAT
11.2 DEGF
SAT DISCHARGE TEMP
112.1 DEGF
DISCHARGE SUPERHEAT
33.4 DEGF
SLIDE VALVE STEP
COOLER INLET REFRIG
23.6 DEGF
LIQUID LINE SOLENOID
ECONOMIZER TXV SOLENOID
CONDENSER FAN STAGE
COMPRESSOR HEATER
WYE-DELTA RELAY
DAILY SCHEDULE
S M T W T F S
*=HOLIDAY
MON START=00:00AM
STOP=00:00AM
TUE START=00:00AM
STOP=00:00AM
WED START=00:00AM
STOP=00:00AM
THU START=00:00AM
STOP=00:00AM
FRI START=00:00AM
STOP=00:00AM
SAT START=00:00AM
STOP=00:00AM
HOL START=00:00AM
STOP=00:00AM
The System Cooler Inlet Refrigerant
Temperature will be printed if the unit
is in R-407C mode.
YORK INTERNATIONAL
ON
70
ON
ON
3
OFF
ON

Advertisement

Table of Contents
loading

Table of Contents