Ycas0605Eb - York eco2 YCAS0425EB Installation Operation & Maintenance

Air-cooled screw liquid chillers
Table of Contents

Advertisement

Technical Data
All dimensions are in
mm unless otherwise
noted.
CONTROL ENTRY
(12) 13
CONDUIT K.O.'S
229
ALTERNATIVE
POWER OPENING
(DO NOT USE
unless 2-compressor
multiple point power)
POWER: MULTIPLE POINT WITH TERMINAL BLOCKS
NOTES:
1. Placement on a level surface free of obstructions (including snow, for winter operation) or air recirculation ensures rated performance,
reliable operation and ease of maintenance. Site restrictions may compromise minimum clearances indicated below, resulting in unpre-
dictable air flow patterns and possible diminished performance. YORK's unit controls will optimize operation without nuisance high pres-
sure safety cutout; however, the system designer must consider potential performance degradation. Access to the unit control center
assumes the unit is no higher than on spring isolators. Recommended minimum clearances: Side to wall - 2m; rear to wall - 2m; control
panel end to wall - 1.2m; top - no obstructions allowed; distance between adjacent units - 3m. No more than one adjacent wall may be
higher than the unit..
78
DIMENSIONS – YCAS0605EB
711
51
120
51 TYP.
VIEW B-B
SYS.#1
COILS
(178 WIDE x
533 HIGH)
unit with
178
CONTROL
OPENING
(229 HIGH)
51
305
RECOMMENDED
POWER
OPENING
(533 HIGH)
VIEW C-C
MICRO-COMPUTER
SYS.#2
CONTROL CENTER
COILS
OPTIONS PANEL
B
B
C
438
CONTROL
C
TRANSFORMER
SERVICE SWITCH
49 (EDGE OF
UNIT TO COOLER
CONNECTION)
2321
VIEW A-A
1067
800
191
LD04701
LD04702
YORK INTERNATIONAL