Mitsubishi Electric CITY MULTI PLFY-M-VEM Series Installation Manual page 5

For building application, indoor unit, for use with the r32/r410a
Hide thumbs Also See for CITY MULTI PLFY-M-VEM Series:
Table of Contents

Advertisement

Available languages

Available languages

3. Installing the indoor unit
950 D
20 – 45
860 – 910 C
795 B
145
193
222
G
F
E
Fig. 3-2
A
B
A
E
A
90 100 100 90
70°
F
350
I
Fig. 3-3
20 – 45
145
840 A
E
F
Min. 1500
H
Floor
C
P
C
A
O
D
A
J
K
120°
N
G
H
3.2. Ceiling openings and suspension bolt installation
locations (Fig. 3-2)
Warning:
• This unit should be installed in rooms which exceed the floor space specified
in outdoor unit installation manual.
Refer to outdoor unit installation manual.
• Install the indoor unit at least 2.5 m above floor or grade level.
For appliances not accessible to the general public.
• Refrigerant pipes connection shall be accessible for maintenance purposes.
• Using the installation template (top of the package) and the gauge (supplied as an
accessory with the grille), make an opening in the ceiling so that the main unit can
be installed as shown in the diagram. (The method for using the template and the
gauge is shown.)
* Before using, check the dimensions of template and gauge, because they
change due to fluctuations of temperature and humidity.
* The dimensions of ceiling opening can be regulated within the range shown in
Fig. 3-2; so center the main unit against the opening of ceiling, ensuring that the
respective opposite sides on all sides of the clearance between them becomes
identical.
• Use M10 (3/8") suspension bolts.
* Suspension bolts are to be procured at the field.
• Install securely, ensuring that there is no clearance between the ceiling panel &
grille, and between the main unit & grille.
A Outer side of main unit
B Bolt pitch
C Ceiling opening
D Outer side of Grille
*
Note that the space between ceiling panel of the unit and ceiling slab and etc must be 7 mm
or more.
*
When the optional multi-functional casement is installed, add 135 mm to the dimensions
marked on the figure.
Models
20, 25, 32, 40, 50, 63, 80
100, 125
3.3. Branch duct hole and fresh air intake hole
(Fig. 3-3)
At the time of installation, use the duct holes (cut out) located at the positions shown
in Fig. 3-3, as and when required.
• A fresh air intake hole for the optional multi function casement can also be made.
Note:
• The figure marked with * in the drawing represent the dimensions of the main
unit excluding those of the optional multi function casement. When installing
the optional multi function casement, add 135 mm to the dimensions marked
on the figure.
• When installing the branch ducts, be sure to insulate adequately. Otherwise
condensation and dripping may occur.
• When installing the fresh air intake hole, be sure to remove the insulator P
that is pasted on the indoor unit.
• When external air is input directly through the main unit, intake-air volume
should be 5% or less of indoor unit air volume.
L
• To input the external air, the duct fan and dust collecting filter to prevent
drawing in dust and other particles are necessary.
For details, see "Fresh air intake volume & static pressure characteristics"
M
in the City Multi DATA BOOK.
• When external air is input into the main unit, the operation noise can be larger.
A Branch duct hole
B Main unit
C Fresh air intake hole
D Drain pipe
E Refrigerant pipe
F Branch duct hole diagram
(view from either side)
G 14-4×10 tapping screws
H ø150 cut out hole
E Grille
F Ceiling
G Multi function casement (option)
H Entire periphery
(mm)
A
B
241
258
281
298
I ø175 burring hole pitch
J Fresh air intake hole diagram
K 3-4×10 tapping screws
L ø125 burring hole pitch
M ø100 cut out hole
N Ceiling
Detailed figure of removing the insulator
O
P
Insulation
en
3