5. Electrical work
5.3. Types of control cables
1. Wiring transmission cables
Types of transmission cable
Shielding wire CVVS or CPEVS
Cable diameter
More than 1.25 mm²
Length
Less than 200 m
2. M-NET Remote control cables
Types of remote control cable Shielding wire MVVS
Cable diameter
0.5 to 1.25 mm²
Add any portion in excess of 10 m to within the
Length
longest allowable transmission cable length 200 m
1
B
A
M1 M2
M1 M2
S
1
2
TB3
TB5
B
A
2
M1 M2
M1 M2
TB3
TB5
C
3
B
Pair No.
D
Pair No.
Fig. 5-5
A
BRANCH
10s
1s
SW21
No.
DIGIT
DIGIT
ON
OFF
1
6
SW14 SW12 SW11
Fig. 5-6
A
M1 M2
S
1
2
TB15 TB5
TB15
C
C
A
S
M1 M2
S
TB5
C
A
E
SW22
SW1
SW2
SW3
ON
OFF
1
4
1
0
1
6
1
0
3. MA Remote control cables
Types of remote control cable 2-core cable (unshielded)
Cable diameter
0.3 to 1.25 mm²
Length
Less than 200 m
5.4. Connecting remote controller, indoor and outdoor
transmission cables (Fig. 5-5)
• Connect indoor unit TB5 and outdoor unit TB3. (Non-polarized 2-wire)
The "S" on indoor unit TB5 is a shielding wire connection. For specifications about
the connecting cables, refer to the outdoor unit installation manual.
• Install a remote controller following the manual supplied with the remote controller.
• Connect the remote controller's transmission cable within 10 m using a 0.75 mm
core cable. If the distance is more than 10 m, use a 1.25 mm
1 MA Remote controller
• Connect the "1" and "2" on indoor unit TB15 to a MA remote controller. (Non-polarized
2-wire)
• DC 9 to 13 V between 1 and 2 (MA remote controller)
2 M-NET Remote controller
• Connect the "M1" and "M2" on indoor unit TB5 to a M-NET remote controller. (Non-
polarized 2-wire)
• DC 24 to 30 V between M1 and M2 (M-NET remote controller)
3 Wireless remote controller (When installing wireless signal receiver)
• Connect the wire of wireless signal receiver (9-pole cable) to CN90 of indoor con-
troller board.
• When more than two units are run under group control using wireless remote
controller, connect TB15 each with the same number.
• To change Pair No. setting, refer to installation manual attached to wireless remote
controller. (In initial setting of indoor unit and wireless remote controller, Pair No.
is 0.)
A Terminal block for indoor transmission cable
B Terminal block for outdoor transmission cable (M1(A), M2(B),
C Remote controller
D wireless signal receiver
E wireless remote controller
5.5. Setting addresses (Fig. 5-6)
(Be sure to operate with the main power turned OFF.)
• There are 2 types of rotary switch setting available: setting addresses 1 to 9 and
over 10, and setting branch numbers.
How to set addresses
1
Example: If Address is "3", remain SW12 (for over 10) at "0", and match SW11
(for 1 to 9) with "3".
How to set branch numbers SW14 (Series R2 only)
2
Match the indoor unit's refrigerant pipe with the BC controller's end connection
number.
Remain other than series R2 at "0".
• The rotary switches are all set to "0" when shipped from the factory. These switches
can be used to set unit addresses and branch numbers at will.
• The determination of indoor unit addresses varies with the system at site. Set them
referring to the Data Book.
Controller board
A
• Rotary switches (SW11, SW12 and SW14) in the picture show "0".
2
junction cable.
2
(S))
en
9

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents