7-3 Error code and LED display

An error code displayed on the remote controller (PZ-01RC or PZ-61DR-E) or the M-NET system controllers,
and blinking or illumination of LED11 (green) on PCB B of the Dx-coil unit show the type of an error.
This system is comprised of each control circuit of the Dx-coil unit (PCB A and PCB B), Lossnay unit, and
outdoor unit. If an error occurs, an error code is displayed on the connected remote controller. However, error
codes to be displayed differ depending on error locations and the connected remote controllers.
• Dx-coil unit remote controller (PZ-01RC) uses two-digit codes to indicate errors detected on PCB A of the Dx-
coil unit or in the outdoor unit. Whatever error detected on PCB B of the Dx-coil unit or in the Lossnay unit is
displayed by the error code "P1."
• Lossnay remote controller (PZ-61DR-E) or M-NET system controllers use four-digit codes to indicate errors
detected on PCB B of the Dx-coil unit or in the Lossnay unit. Whatever error detected on PCB A of the Dx-
coil unit or in the outdoor unit is displayed by the error code "0206."
When Lossnay remote controller (PZ-61DR-E) or M-NET system controllers are not connected, error details
can be checked by LED11 (green) on PCB B of the Dx-coil unit.
No. Remote controller Error code
1 Error display on
PZ-01RC
2 Error display on
PZ-61DR-E and
M-NET system
controllers
No. 1. Error code displayed on Dx-coil unit remote controller (PZ-01RC)
An error is detected
on PCB A of the
Dx-coil unit or in the
Outdoor unit.
Displays an error code
other than "P1"
No. 2. Error code displayed on Lossnay remote controller (PZ-61DR-E) or the M-NET system controllers
An error is detected
on PCB A of the
Dx-coil unit or in the
Outdoor unit.
Displays the error
code "0206".
Other than
An error is detected on PCB
"P1"
A of the Dx-coil unit or in the
Outdoor unit.
"P1"
An error is detected on PCB
B of the Dx-coil unit or in the
Lossnay unit.
"0206"
An error is detected on PCB
A of the Dx-coil unit or in the
Outdoor unit.
Other than
An error is detected on PCB
"0206"
B of the Dx-coil unit or in the
Lossnay unit.
Mr. Slim
Outdoor unit
Dx-coil unit
PCB A
Dx-coil unit remote controller
PZ-01RC
Mr. Slim
Outdoor unit
Dx-coil unit
PCB A
Dx-coil unit remote controller
Note: Dx-coil unit remote controller (PZ-01RC) displays an error code as well as the case of No. 1.
Cause
See (1).
When Lossnay remote controller (PZ-61DR-E)
or M-NET system controllers are used, check
an error code displayed on them. → See (3).
If none of them are used, check LED11 on
PCB B of the Dx-coil unit. → See (2).
Check an error code displayed on Dx-coil unit
remote controller (PZ-01RC).
If the error code "P1" is displayed, check cable
connection or power supply referring to the er-
ror code "0206" troubleshooting. → See (3).
See (3).
Lossnay
PCB B
Lossnay
PCB B
Lossnay remote controller
PZ-61DR-E
PZ-01RC
─ 15 ─
Corrective action
M-NET
An error is detected
on PCB B of the
Dx-coil unit or in the
Lossnay unit.
Displays the error
code "P1"
M-NET
An error is detected on
PCB B of the Dx-coil
unit or in the Lossnay
unit.
Displays an error code
other than "0206".