Technical description

11.19.5 How is controlled the condenser fan

A pressure probe BP2 is located on the discharge side of the compressor. The condenser fan is activated (ON) when
the BP2 pressure is higher than FANon setting (R134a approx. 11 barg/160 psig – R407C approx. 18 barg/260 psig) and
led
is ON. Condenser fan stops when BP2 pressure is lower than FANoff setting (R134a approx. 8 barg/115 psig
– R407C approx. 14 barg/203 psig).

11.19.6 How is controlled the drain solenoid valve

Drain solenoid valve is activated (ON) for
Led
shows that condensate drain solenoid valve is ON.
The condensate drain test is always active using the button
NOTE : if an electronic drainer is installed, DMC34 is set to keep always powered the drain output (

11.19.7 How to reset the service reminder timer

With dryer OFF keep pressed buttons
switch (pos.1 paragraph 7.1).
After 5 seconds display shows
seconds. Timer has been reset and controller start to operate regularly.
Service reminder timing can be reset at any time, even before the timing has expired.

11.19.8 Operation of the failure / alarm dry contact

The DMC34 is equipped with a dry contact (potential free) to display failure and/or alarm conditions.
Dryer powered and no service warning / alarm is active.
8
9
Dryer not powered or service warning / alarm is active.
8
9

11.19.9 How to change the operating parameters

The setup menu can be used to change the dryer's operating parameters.
Only qualified personnel must be allowed to access to the setup menu. The manufacturer is not
responsible for malfunctioning or failure due to modification to the operating parameters.
With dryer ON simultaneously press buttons
Access to the menu is confirmed by message
Set
Keep
pressed to display the value of the selected parameter and use arrows
change the value. Release the button
Press
+
automatically).
ID
Ton – drain time ON : time ON condensate drain valve
ON = Electronic drainer installed
ToF - drain time OFF : pause time for condensate drain valve
HdS – High DewPoint Setting : Alarm threshold for a high
DewPoint (the alarm disappears when the temperature drop
1°C / 2°F below alarm point)
Hdd - High DewPoint Delay : high DewPoint alarm enable
delay
SrV - Service Setting: setting of service warning timer.
00 = service warning timer disabled.
SrC – Service Contact : configuration of the alarm dry contact
for the service warning timer.
YES = activate the contact / NO = NOT activate the contact
SCL - Scale: display scale of temperatures and pressure (°C
= temperatures in °C and pressure in barg; °F = temperatures
in °F and pressure in psig)
30
seconds (standard 2 seconds) every
Set
+
, release buttons
Set
+
on the display (first parameter of menu).
Set
to confirm the value and skip to following parameter.
to exit setup menu (if no button is pressed after 2 minutes the menu is exited
Description
.
, power the dryer and switch it on using the ON-OFF
Set
+
, keep pressed button
for at least 5 seconds to enter the setup menu.
Limits
ON
00 ... 20 sec
1 ... 20 min
0.0...25.0 °C
or
32 ... 77 °F
01 ... 20
minutes
00.0 ... 20.0
(x 1000) hours
YES / NO
°C ... °F
DRYPOINT® RS 15-550 HP50 NA
minutes (standard 1 minute).
= ON).
for 5
and
Standard
Resolution
setup
1 sec
2
1 min
1
0.5 °C
20
or
or
1 °F
68
1 min
15
0.5
(x1000)
08.0
hours
-
YES
-
°C
to

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents