Connection To The Compressed-Air System; Connection To The Cooling-Water Network; Minimum Cooling Water Requirements - Beko DRYPOINT RS HP50 NA Series Instructions For Installation And Operation Manual

High pressure compressed air refrigeration dryer
Table of Contents

Advertisement

8.4

Connection to the compressed-air system

Danger!
Compressed air!
All works must only be carried out by qualified skilled personnel.
Never work on compressed-air systems which are under pressure.
The operator or the user must ensure that the dryer is never operated with a pressure exceeding the
maximum pressure value indicated on the name plate.
Exceeding the maximum operating pressure can be dangerous for the operator but also for the device.
The air temperature and the air flow at the inlet of the dryer must lie within the limit values indicated on the name plate.
The connecting lines must be free from dust, iron rust, shards and other contaminations and correspond to the flow rate
of the dryer. Should air with a very high temperature be treated, the installation of an aftercooler may be necessary. For
the implementation of maintenance works, the installation of a bypass system is recommended.
Note!
Pulsation and vibrations!
Pulsations and vibrations must be eliminated from the compressed air and IN/OUT piping to avoid possible
fatigue failure.
Do not use the dryer to treat air containing corrosive substances for copper and its alloys..
===== Ende der Stüc kli ste =====
Note!
Contaminated intake air!
In the event that the intake air is strongly contaminated (ISO 8573.1 class 3.-3) or poorer quality, we
recommend the additional installation of a prefilter (e.g. CLEARPOINT HP50S040), to avoid clogging of
the heat exchanger.
8.5

Connection to the cooling-water network

Danger!
Compressed air and unqualified personnel!
All works must only be carried out by qualified skilled personnel.
Never work on compressed-air systems which are under pressure.
The user must ensure that the dryer is never operated with a pressure exceeding the nominal values.
Possible overpressure can be dangerous for the operator but also for the device.
The temperature and the amount of cooling water need to correspond to the limit values indicated on the name plate.
The cross-section of the connecting lines, which should preferably be flexible, must be free from dust, iron rust, shards
and other contaminations. We recommend employing connecting lines (flexible hoses, vibration-inhibiting fittings etc.)
which protect the dryer against possible vibrations in the pipework.
Note!
Contaminated intake water!
In the event that the intake water is strongly contaminated we recommend the additional installation of a
prefilter (500 micron), to avoid clogging of the heat exchanger.
8.6

Minimum cooling water requirements:

Temperature
Pressure
Delivery pressure
Total hardness
PH
Conductivity
Residual solids
Saturation mark SI
HCO
3
2-
SO
4
(1) – Other temperatures upon request – check the data on the name plate.
Note:
(2) – Other pressures upon request – check the data on the name plate.
(3) – Pressure difference at the water connection of the dryer at maximum water flow.
Other delivery pressures upon request.
CAUTION!
During the piping of the dryer, the inlet and outlet connections need to be supported as is shown in the
illustration.
Non-observance will cause damage.
DRYPOINT® RS 15-550 HP50 NA
59...86°F (15...30°C) (1)
44...145 psig (3...10 barg) (2)
> 44 psig (3 bar) (2) (3)
6.0...15 dH°
7.5...9.0
10...500 μS/cm
<30 mg/l or ppm
-0.2 < 0 < 0.2
70...300 mg/l or ppm
<70 mg/l or ppm
HCO
/ SO
>1.0 mg/l or ppm
3
4
NH
<2 mg/l or ppm
3
-
Cl
50 mg/l or ppm
Cl
0.5 mg/l or ppm
2
H
S
<0.05 mg/l or ppm
2
CO
<5 mg/l or ppm
2
NO
<100 mg/l or ppm
3
Fe
<0.2 mg/l or ppm
Al
<0.2 mg/l or ppm
Mn
<0.1 mg/l or ppm
Installation
15

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents