Communication Management for SIMATIC S7
Table 7-1
Network parameter
Network parameter
TP address
Protocol
Baud rate
S7-200 address
HSA
Data types supported
The data types listed in table 7-2 are available for the configuration of tags.
Table 7-2
Data types available
Data type
Tag
Input
Output
Flag
Timer
Counter
7-4
Explanation
Address of the TP 070
The protocol profile used in the network configuration.
Set MPI or DP here.
The baud rate at which communication takes place
over the network.
Address of the S7 module (CPU) to which the TP 070
is connected.
Highest Station Address; this must be identical
throughout the whole network configuration.
Data types supported for S7–200
Addressed by
V
I
Q
M
T
C
Format
BYTE, INT, WORD,
DINT, DWORD, REAL,
BOOL, STRING
BYTE, INT, WORD,
DINT, DWORD, REAL,
BOOL, STRING
BYTE, INT, WORD,
DINT, DWORD, REAL,
BOOL, STRING
BYTE, INT, WORD,
DINT, DWORD, REAL,
BOOL, STRING
TIMER
COUNTER
TP 070 Equipment Manual
Release 03/00