A.1 AFP-200
A.1.1 General
The UDACT-2 is capable of reporting a maximum of 99 zones when used with the AFP-200.For the UDACT-2 to correctly report a zone
to the Central Station, both the panel and the UDACT-2 must have each zone programmed as the same function type (refer to "Zone and
Point Assignments" on page 26). If a UDACT-2 point does not match the panel point in function, the point will default to fire alarm and
a fire alarm signal will be transmitted to the Central Station.
For more information on the AFP-200 see the AFP-200 Instruction Manual.
A.1.2 Mounting
Since the AFP-200 does not accommodate the UDACT-2 in the control panel enclosure, the UDACT-2 must be mounted remotely using
an ABS-8RB, UBS-1B, or UBS-1R. The unit must be placed within the same room and within 20 feet (6.1 meters) of the panel. Wiring
must be enclosed in conduit. Refer to "Remote Installation" on page 17 for installation instructions.
A.1.3 Wiring
CAUTION:
!
REMOVE ALL POWER FROM THE CONTROL PANEL BY DISCONNECTING AC AND BATTERIES BEFORE MAKING
ANY CONNECTIONS TO PREVENT PERSONAL AND/OR CIRCUIT DAMAGE.
Connections
Refer to Figure A.1.
Connect the communication line between the EIA-485 terminal block TB5 on the AFP-200 and TB2 terminals +EIA-485 and -EIA-485
on the UDACT-2, being certain to observe polarity.
If the UDACT-2 is the only or last device connected to the EIA-485, set SW1 DIP 1:4 to ON to enable the UDACT-2's 120 ohm termi-
nating resistor.
Connect the Ground Wire (PN 71073, provided) from the UDACT-2 earth terminal on TB2 to a solid building earth ground.
Connect 24VDC filtered, non-resettable power from terminal block TB1 on the AFP-200 to TB1 +24V and Common terminals on the
UDACT-2.
Notes
1.
Recommended wire is 12 AWG (3.25mm
shield may be connected to a Common Terminal at TB2 on the UDACT-2 as shown in Figure A.1.
NOTE: The shield end that is not connected should be insulated to prevent accidental grounding. Do not connect both ends of
shield under any circumstance since a ground fault may result.
2.
Conduit is required for external wire runs. Consult local building codes.
3.
Refer to "Specifications" on page 8 for power requirements.
UDACT-2 — Instruction Manual P/N 54089:B3 10/29/2019

Appendix A: Panel-Specific Information

2
) to 18 AWG (0.75mm
2
) twisted pair, shielded cable. Connect only one end of shield:
34