For example, assume the system is a heat pump matched with an
air handler. With a call for low stage cooling, the heat pump will
calculate the system's low stage cooling airflow demand. The
heat pump will then send a fan request along with the low stage
cooling airflow demand to the air handler. Once received, the air
handler will send the low stage cooling airflow demand to the
ECM motor. The ECM motor then delivers the low stage cooling
airflow. The table at right lists the nominal high and low stage
airflow for the ComfortNet™ heat pumps.
Models
High
DZ16TC0241
800
DZ16TC0361
1200
DZ16TC0481
1550
DZ16TC0601
1800
DZ18TC0241
850
DZ18TC0361
1250
DZ18TC0481
1750
DZ18TC0601
1750
C
W
ONTROL
IRING
NOTE:
Refer to section Electrical Connections - High Voltage
Connections for 208/230 volt line connections to the air conditioner
or heat pump.
NOTE:
A removable plug connector is provided with the control
board
to make thermostat wire connections. This plug may be
removed, wire connections made to the plug, and replaced. It is
strongly recommended that you do not connect multiple wires
into a single terminal. Wire nuts are recommended to ensure one
wire is used for each terminal. Failure to do so may result in
intermittent operation.
Airflow
Mode
Demand Source
Heat Pump
Heat Pump
Only
> of Heat Pump or Air
Strips
Handler Demand
Air Handler
Only
Thermostat
Heat Pump
Heat Pump
Only
Furnace
Thermostat
Cooling
Heating
Low
High
600
800
800
1200
1100
1550
1210
1800
550
850
850
1250
1210
1750
1210
1750
Typical 18 AWG thermostat wire may be used to wire the system
components. 150 feet is the maximum recommended length of
wire between indoor unit and outdoor unit, or between indoor
unit and thermostat.
When installed as a communicating system, only data lines 1 and
2 are required between the indoor and outdoor units.
R
C
Optional
G
Optional
Y
Optional if
feature
supported by
thermostat
L
C
EGACY
ONTROLS
The intergrated control board on this unit is factory-equipped
with a 4-pin connector for low voltage contols wiring for commu-
nicating systems. If the system is installed as a non-communicat-
ing (legacy) system, remove the 4-pin connector and disconnect
the transformer low voltage and line voltage wiring. Then, install
the 7-pin connector that is supplied in the literature/accessories
Low
bag into the intergrated control board in the appropriate location
600
indicated by the color-coded labels found on both the control
800
board and pin connector plug.
1100
R
C
1210
550
850
R
C
1
2
1210
1210
R
C
C
N
™ S
OMFORT
ET
The ComfortNet system permits access to additional system infor-
mation, advanced setup features, and advanced diagnostic/
troubleshooting features. See indoor equipment installation
manual for directions on how to access the menus.
9
OUTDOOR
INDOOR
BOARD TERMINAL
BOARD TERMINAL
CONNECTIONS
CONNECTIONS
1
1
2
2
C
C
R
C
G
Y
W
IRING
G
O
G
O
G
O
System Wiring for legacy controls