TROUBLESHOOTING INFORMATION: UNITARY DIAGNOSTIC CODES
S ym pt o ms o f A bno rm a l
O pe ra t io n
( Le ga c y & C o m f o rt N e t ™
T he rm o s t a t )
• A ir co nditio ner/heat pump
fails to o perate.
• Integrated co ntro l mo dule
diagno stic/status LED display
sho ws the indicated co de.
• A ir co nditio ner/heat pump
fails to o perate.
• Integrated co ntro l mo dule
diagno stic/status LED display
sho ws the indicated co de.
• Very lo ng run time.
• Fo ur co nsecutive
co mpresso r pro tecto r trips with
average run time between trips
greater than 3 ho urs.
• Co mpresso r o perating at high
speed and o utdo o r fan
o perating at lo w speed
• Integrated co ntro l mo dule
diagno stic/status LED display
sho ws the indicated co de.
• Co mpresso r and o utdo o r fan
are o ff.
• Thermo stat demand is
present.
• Integrated co ntro l mo dule
diagno stic/status LED display
sho ws the indicated co de.
UNITARY DIAGNOSTIC CODES
D ia gno s t ic / S t a t us
LE D D is pla v C o de s
D igit 3
D igit 2
D igit 1
B LA NK
d
3
B LA NK
d
4
B LA NK
0
1
B LA NK
0
1
F a ult
P o s s ible
D e s c ript io n
C a us e s
• Co nfiguratio n
• Shared data sent
M is-match
to integrated
co ntro l mo dule
do es no t match
hardware
co nfiguratio n.
• Invalid M emo ry
• Shared data o n
Card Data
memo ry card has
been rejected.
• Lo w Side Fault
• Lo w refrigerant
charge.
• Restrictio n in
liquid line.
• Indo o r blo wer
mo to r failure.
• Indo o r
thermo stat set
extremely lo w.
• Lo w ressure Cut
• Lo w refrigerant
Out Trip
charge.
• Restrictio n in
liquid line.
• Indo o r blo wer
mo to r failure.
• Indo o r
thermo stat set
extremely lo w.
16
C o rre c t iv e
N o t e s &
A c t io ns
C a ut io ns
• Verify system
• Turn po wer OFF
type
prio r to repair.
(co mmunicating
• Use memo ry card fo r
o r legacy).
yo ur specific mo del.
• Verify shared
• Insert memo ry card
data is co rrect fo r
B EFORE turning
yo ur specific
po wer ON. M emo ry
mo del; re-
card may be remo ved
po pulate data if
after data is lo aded.
required.
Turn po wer OFF
• Wire system as
befo re remo ving
legacy system.
memo ry card.
• Erro r co de will be
cleared o nce data is
lo aded.
• Verify system
• Turn po wer OFF
type
prio r to repair.
(co mmunicating
• Use memo ry card fo r
o r legacy).
yo ur specific mo del.
• Verify shared
• Insert memo ry card
data is co rrect fo r
B EFORE turning
yo ur specific
po wer ON. M emo ry
mo del; re-
card may be remo ved
po pulate data if
after data is lo aded.
required.
Turn po wer OFF
• Wire system as
befo re remo ving
legacy system.
memo ry card.
• Erro r co de will be
cleared o nce data is
lo aded.
• Verify refrigerant
• Turn po wer OFF
charge; adjust as
prio r to repair.
needed.
• Fault will clear after
•Check fo r
3 co nsecutive no rmal
restricted liquid
cycles.
line; repair/
• Fault may be cleared
replace as
by cycling 4V A C to
needed.
co ntro l.
• Check indo o r
• Replace with co rrect
blo wer mo to r;
replacement part(s).
repair/replace as
needed.
• Check indo o r
thermo stat
setting.
• Verify refrigerant
• Turn po wer OFF
charge; adjust as
prio r to repair.
needed.
• Replace with co rrect
•Check fo r
replacement part(s).
restricted liquid
line; repair/
replace as
needed.
• Check indo o r
blo wer mo to r;
repair/replace as
needed.
• Check lo w
pressure switch;
repair/replace as
needed.
• Check indo o r
thermo stat
setting.