5.14.1. Connection inputs of the OR logic ............. 48 Elsner Elektronik GmbH • Sohlengrund 16 • 75395 Ostelsheim • Germany Sensors Intra-Sewi KNX T and Intra-Sewi KNX TH • from version 1.0 Version: 11.06.2018 • Technical changes and errors excepted.
Page 4
Clarification of signs Installation, inspection, commissioning and troubleshooting of the device must only be carried out by a competent electrician. This manual is amended periodically and will be brought into line with new software releases. The change status (software version and date) can be found in the contents footer. If you have a device with a later software version, please check www.elsner-elektronik.de in the menu area "Service"...
Elsner Elektronik website on www.elsner-elektronik.de in the “Ser- vice” menu. 1.0.1. Scope of delivery • Sensor • Pre-assembled clamps for false ceiling installation Sensors Intra-Sewi KNX T and Intra-Sewi KNX TH • Version: 11.06.2018 • Technical changes and errors excepted.
The device may only be used as a fixed-site installation; that means only when assem- bled and after conclusion of all installation and operational start-up tasks and only in the surroundings designated for it. Sensors Intra-Sewi KNX T and Intra-Sewi KNX TH • Version: 11.06.2018 • Technical changes and errors excepted.
Place the device in the installation opening in the ceiling. For this, fold the clamps up- wards and guide the device through the installation opening with the clamps first. Intra-Sewi KNX T(H) is automatically fixed by the clamps. Sensors Intra-Sewi KNX T and Intra-Sewi KNX TH • Version: 11.06.2018 • Technical changes and errors excepted.
Clamp the device in the support ring so that the springs on the device snap over the tabs of the support ring. Fig. 2: Support ring Tabs Sensors Intra-Sewi KNX T and Intra-Sewi KNX TH • Version: 11.06.2018 • Technical changes and errors excepted.
The connection is made with the KNX terminal (red/black) to KNX TP. Fig. 4 Clamps for installation in false ceiling Springs for installation in sup- port ring KNX terminal Sensors Intra-Sewi KNX T and Intra-Sewi KNX TH • Version: 11.06.2018 • Technical changes and errors excepted.
The airing lamella must not get dirty or covered. As a rule, it is sufficient to wipe the device with a soft, dry cloth twice a year. Sensors Intra-Sewi KNX T and Intra-Sewi KNX TH • Version: 11.06.2018 • Technical changes and errors excepted.
Page 12
Maintenance Sensors Intra-Sewi KNX T and Intra-Sewi KNX TH • Version: 11.06.2018 • Technical changes and errors excepted.
The device sends all outputs according to their send behaviour set in the parameters with the delays established in the "General settings" parameter block. Sensors Intra-Sewi KNX T and Intra-Sewi KNX TH • Version: 11.06.2018 • Technical changes and errors excepted.
"Reset temperature min/max. value" objects to reset the values to the current readings. The values are not retained after a reset. Use minimum and maximum value No • Yes Sensors Intra-Sewi KNX T and Intra-Sewi KNX TH • Version: 11.06.2018 • Technical changes and errors excepted.
Page 25
Starting heating/cooling setpoint (in 0.1 °C) -300…800; 210 valid until 1st communication (not upon saving the setpoint value after programming) Sensors Intra-Sewi KNX T and Intra-Sewi KNX TH • Version: 11.06.2018 • Technical changes and errors excepted.
Page 26
0…200; 30 (for heating) Increase cooling setpoint (in 0.1°C) 0…200; 30 (for cooling) Eco setpoint Eco mode is usually used for night mode. Sensors Intra-Sewi KNX T and Intra-Sewi KNX TH • Version: 11.06.2018 • Technical changes and errors excepted.
Page 27
• common control variable are used for Level 1+2 Use control variable for 4/6-way valve No • Yes (only for common control variables in level 1) Sensors Intra-Sewi KNX T and Intra-Sewi KNX TH • Version: 11.06.2018 • Technical changes and errors excepted.
During initial commissioning, a threshold value must be defined, which will be valid until the first communication with a new threshold value. For units which have already Sensors Intra-Sewi KNX T and Intra-Sewi KNX TH • Version: 11.06.2018 • Technical changes and errors excepted.
Page 29
• on change to 0 and periodically Cycle 5 s • 10 s • 30 s… • 2 h (only if sending periodically is selected) Sensors Intra-Sewi KNX T and Intra-Sewi KNX TH • Version: 11.06.2018 • Technical changes and errors excepted.
In the 2nd level (therefore only in case of 2-level heating), heating is controlled via a PI or a 2-point-control. Sensors Intra-Sewi KNX T and Intra-Sewi KNX TH • Version: 11.06.2018 • Technical changes and errors excepted.
Page 31
This setting provides fixed parameters for frequent applications. Control type • PI control Setting of the controller by • Controller parameter • specified applications Sensors Intra-Sewi KNX T and Intra-Sewi KNX TH • Version: 11.06.2018 • Technical changes and errors excepted.
Page 32
1 bit object (on/off) or an 8 bit object (on with percentage/off). Control variable is a • 1 bit object • 8 bit object Value (in %) 0...100 (for 8 bit object) Sensors Intra-Sewi KNX T and Intra-Sewi KNX TH • Version: 11.06.2018 • Technical changes and errors excepted.
You should set the time appropriate to the cooling system at this point (observe manufacturer's instructions). Maximum control variable is reached 1...5 at setpoint/actual difference of (in °C) Reset time (in min.) 1...255; 30 Sensors Intra-Sewi KNX T and Intra-Sewi KNX TH • Version: 11.06.2018 • Technical changes and errors excepted.
Page 34
1 bit object (on/off) or an 8 bit object (on with percentage/off). Control variable is a • 1 bit object • 8 bit object Value (in %) 0...100 (for 8 bit object) Sensors Intra-Sewi KNX T and Intra-Sewi KNX TH • Version: 11.06.2018 • Technical changes and errors excepted.
"Reset humidity min/max. value" objects to reset the values to the current readings. The values are not retained after a reset. Use minimum and maximum value No • Yes Sensors Intra-Sewi KNX T and Intra-Sewi KNX TH • Version: 11.06.2018 • Technical changes and errors excepted.
Sensors Intra-Sewi KNX T and Intra-Sewi KNX TH • Version: 11.06.2018 • Technical changes and errors excepted.
Page 37
Use switching output block No • Yes If the block is activated, define specifications here for the behaviour of the output when blocked. Sensors Intra-Sewi KNX T and Intra-Sewi KNX TH • Version: 11.06.2018 • Technical changes and errors excepted.
Type of control • One-level dehumidification • Two-level dehumidification • Humidification and dehumidification Configure a block for the humidity control using the blocking object. Sensors Intra-Sewi KNX T and Intra-Sewi KNX TH • Version: 11.06.2018 • Technical changes and errors excepted.
Page 39
Enter, how the setpoint value will be received from the bus. Basically, a new value can be received, or simply a command to increase or decrease. Sensors Intra-Sewi KNX T and Intra-Sewi KNX TH • Version: 11.06.2018 • Technical changes and errors excepted.
Page 40
In case of a short reset time, the control responds with a fast increase of the control variable. In case of a long reset time, the control responds somewhat less Sensors Intra-Sewi KNX T and Intra-Sewi KNX TH • Version: 11.06.2018 • Technical changes and errors excepted.
(offset/deviation). The switching output of the coolant temperature monitoring system can provide a warning prior to any build-up of conden- sation in the system, and/or activate appropriate countermeasures. Sensors Intra-Sewi KNX T and Intra-Sewi KNX TH • Version: 11.06.2018 • Technical changes and errors excepted.
Page 42
(if sent on change) Send cycle 5 s • 10 s • 30 s • 1 min • … • 2 h (if sent periodically) Sensors Intra-Sewi KNX T and Intra-Sewi KNX TH • Version: 11.06.2018 • Technical changes and errors excepted.
Page 43
• if switching output = 1 send 1 Switching output sends on change to 0 • Do not send message • if switching output = 0 send 0 Sensors Intra-Sewi KNX T and Intra-Sewi KNX TH • Version: 11.06.2018 • Technical changes and errors excepted.
In this way, it is for example possible to monitor compliance with DIN 1946 (standard values) or even to define your own comfort field. Use comfort field No • Yes Sensors Intra-Sewi KNX T and Intra-Sewi KNX TH • Version: 11.06.2018 • Technical changes and errors excepted.
Determine what the control variable comparator should output, and activate the input objects to be used. Transmission patterns and blocks can also be set. Sensors Intra-Sewi KNX T and Intra-Sewi KNX TH • Version: 11.06.2018 • Technical changes and errors excepted.
AND logic ... not active • active AND logic 4 not active • active OR logic OR logic 1 not active • active Sensors Intra-Sewi KNX T and Intra-Sewi KNX TH • Version: 11.06.2018 • Technical changes and errors excepted.
Temperature sensor malfunction ON Temperature sensor malfunction OFF Switching output 1 Temperature Switching output 1 Temperature inverted Switching output 2 Temperature Switching output 2 Temperature inverted Sensors Intra-Sewi KNX T and Intra-Sewi KNX TH • Version: 11.06.2018 • Technical changes and errors excepted.
The OR logic connection inputs correspond to those of the AND logic. In addition, the following inputs are available for the OR logic: Sensors Intra-Sewi KNX T and Intra-Sewi KNX TH • Version: 11.06.2018 • Technical changes and errors excepted.
Page 51
Switching output AND logic 2 inverted Switching output AND logic 3 Switching output AND logic 3 inverted Switching output AND logic 4 Switching output AND logic 4 inverted Sensors Intra-Sewi KNX T and Intra-Sewi KNX TH • Version: 11.06.2018 • Technical changes and errors excepted.