Clarification of signs Installation, inspection, commissioning and troubleshooting of the device must only be carried out by a competent electrician. This manual is amended periodically and will be brought into line with new software releases. The change status (software version and date) can be found in the contents footer. If you have a device with a later software version, please check www.elsner-elektronik.de in the menu area "Service"...
PI-controller for heating (one or two-stage) and cooling (one or two-stage) according to temperature. Regulation according to separate setpoints or basic setpoint temperature Sensors Sewi KNX AQS and Sewi KNX AQS/TH-D • Version: 10.09.2018 • Technical changes and errors excepted.
After unpacking the device, check it immediately for possible mechanical damage. If it has been damaged in transport, inform the supplier immediately. Sensors Sewi KNX AQS and Sewi KNX AQS/TH-D • Version: 10.09.2018 • Technical changes and errors excepted.
Measurement variations from such sources of interference must be corrected in the ETS in order to ensure the specified accuracy of the sensor (offset). Sensors Sewi KNX AQS and Sewi KNX AQS/TH-D • Version: 10.09.2018 • Technical changes and errors excepted.
2.3.1. Housing from the outside Fig. 1 Recess to open the hous- ing. When closing the housing, the recess aligns to the marking on the skirt- Sensors Sewi KNX AQS and Sewi KNX AQS/TH-D • Version: 10.09.2018 • Technical changes and errors excepted.
2.4. Assembly Fig. 3 Open the housing. To do this, carefully lift the cover from the skirting. Start at the recess (Fig. 2: A). Sensors Sewi KNX AQS and Sewi KNX AQS/TH-D • Version: 10.09.2018 • Technical changes and errors excepted.
After the bus voltage has been applied, the device will enter an initialisation phase last- ing a few seconds. During this phase no information can be received or sent via the bus. Sensors Sewi KNX AQS and Sewi KNX AQS/TH-D • Version: 10.09.2018 • Technical changes and errors excepted.
The air slots on the side must not get dirty or covered. As a rule, it is sufficient to wipe the device with a soft, dry cloth twice a year. Sensors Sewi KNX AQS and Sewi KNX AQS/TH-D • Version: 10.09.2018 • Technical changes and errors excepted.
The device sends all outputs according to their send behaviour set in the parameters with the delays established in the "General settings" parameter block. Sensors Sewi KNX AQS and Sewi KNX AQS/TH-D • Version: 10.09.2018 • Technical changes and errors excepted.
The minimum and maximum readings can be saved and sent to the bus. Use the "Reset temperature min/max. value" objects to reset the values to the current readings. The values are not retained after a reset. Sensors Sewi KNX AQS and Sewi KNX AQS/TH-D • Version: 10.09.2018 • Technical changes and errors excepted.
Sensors Sewi KNX AQS and Sewi KNX AQS/TH-D • Version: 10.09.2018 • Technical changes and errors excepted.
Page 33
Use switching output block No • Yes If the block is activated, define specifications here for the behaviour of the output when blocked. Sensors Sewi KNX AQS and Sewi KNX AQS/TH-D • Version: 10.09.2018 • Technical changes and errors excepted.
Target values and extension time received • never via communication objects • after power supply restoration • after power supply restoration and programming Sensors Sewi KNX AQS and Sewi KNX AQS/TH-D • Version: 10.09.2018 • Technical changes and errors excepted.
Page 35
Send control variable • on change • on change and periodically from change (in % absolute) 1...10; 2 Sensors Sewi KNX AQS and Sewi KNX AQS/TH-D • Version: 10.09.2018 • Technical changes and errors excepted.
Page 36
(with switching object) • 1 = Heating | 0 = Cooling Value of the switching object after reset 0 • 1 (with switching object) Sensors Sewi KNX AQS and Sewi KNX AQS/TH-D • Version: 10.09.2018 • Technical changes and errors excepted.
Page 37
"heating and cooling" to avoid direct switching from he- ating to cooling. Dead zone between heating and cooling 1…100; 50 (only if both heating AND cooling are used) Sensors Sewi KNX AQS and Sewi KNX AQS/TH-D • Version: 10.09.2018 • Technical changes and errors excepted.
Page 38
If the comfort setpoint value is used as a basis, the reduction/increment of the value is set. Reduce heating setpoint (in 0.1°C) 0…200; 50 (for heating) Increase cooling setpoint (in 0.1°C) 0…200; 60 (for cooling) Sensors Sewi KNX AQS and Sewi KNX AQS/TH-D • Version: 10.09.2018 • Technical changes and errors excepted.
In the 2nd level (therefore only in case of 2-level heating), heating is controlled via a PI or a 2-point-control. Sensors Sewi KNX AQS and Sewi KNX AQS/TH-D • Version: 10.09.2018 • Technical changes and errors excepted.
Page 40
This setting provides fixed parameters for frequent applications. Control type • PI control Setting of the controller by • Controller parameter • specified applications Sensors Sewi KNX AQS and Sewi KNX AQS/TH-D • Version: 10.09.2018 • Technical changes and errors excepted.
Page 41
1 bit object (on/off) or an 8 bit object (on with percentage/off). Control variable is a • 1 bit object • 8 bit object Value (in %) 0...100 (for 8 bit object) Sensors Sewi KNX AQS and Sewi KNX AQS/TH-D • Version: 10.09.2018 • Technical changes and errors excepted.
You should set the time appropriate to the cooling system at this point (observe manufacturer's instructions). Maximum control variable is reached 0...5 at setpoint/actual difference of (in °C) Reset time (in min.) 1...255; 30 Sensors Sewi KNX AQS and Sewi KNX AQS/TH-D • Version: 10.09.2018 • Technical changes and errors excepted.
Page 43
1 bit object (on/off) or an 8 bit object (on with percentage/off). Control variable is a • 1 bit object • 8 bit object Value (in %) 0...100 (for 8 bit object) Sensors Sewi KNX AQS and Sewi KNX AQS/TH-D • Version: 10.09.2018 • Technical changes and errors excepted.
"Reset humidity min/max. value" objects to reset the values to the current readings. The values are not retained after a reset. Use minimum and maximum value No • Yes Sensors Sewi KNX AQS and Sewi KNX AQS/TH-D • Version: 10.09.2018 • Technical changes and errors excepted.
Sensors Sewi KNX AQS and Sewi KNX AQS/TH-D • Version: 10.09.2018 • Technical changes and errors excepted.
Page 47
(is only sent if periodically is selected) Block The switching output can be blocked using an object. Use switching output block No • Yes Sensors Sewi KNX AQS and Sewi KNX AQS/TH-D • Version: 10.09.2018 • Technical changes and errors excepted.
Type of control • One-level dehumidification • Two-level dehumidification • Humidification and dehumidification Configure a block for the humidity control using the blocking object. Sensors Sewi KNX AQS and Sewi KNX AQS/TH-D • Version: 10.09.2018 • Technical changes and errors excepted.
Page 49
Enter, how the setpoint value will be received from the bus. Basically, a new value can be received, or simply a command to increase or decrease. Sensors Sewi KNX AQS and Sewi KNX AQS/TH-D • Version: 10.09.2018 • Technical changes and errors excepted.
Page 50
In case of a short reset time, the control responds with a fast increase of the control variable. In case of a long reset time, the control responds somewhat less Sensors Sewi KNX AQS and Sewi KNX AQS/TH-D • Version: 10.09.2018 • Technical changes and errors excepted.
Set, in which cases offset received via object is to be retained. Please note that the set- ting "After power supply restoration and programming" should not be used for the in- Sensors Sewi KNX AQS and Sewi KNX AQS/TH-D • Version: 10.09.2018 • Technical changes and errors excepted.
Page 52
None • 1 s • 2 s • 5 s • 10 s • … • 2 h for setting via objects: valid until 1st communication Sensors Sewi KNX AQS and Sewi KNX AQS/TH-D • Version: 10.09.2018 • Technical changes and errors excepted.
The absolute air humidity value is detected by the Sewi KNX AQS and Sewi KNX AQS/TH-D and can be output to the bus. Sensors Sewi KNX AQS and Sewi KNX AQS/TH-D • Version: 10.09.2018 • Technical changes and errors excepted.
Text for normal pressure range < 98,000 Pa stormy (e.g. weather is stormy) 98,000...100,000 Pa rainy (e.g. weather is rainy) 100,000...102,000 Pa changeable (e.g. weather is changeable) Sensors Sewi KNX AQS and Sewi KNX AQS/TH-D • Version: 10.09.2018 • Technical changes and errors excepted.
The parameter is only taken into consideration if the specification/ setting by object is activated further down. Please note that the setting "After power restoration and pro- Sensors Sewi KNX AQS and Sewi KNX AQS/TH-D • Version: 10.09.2018 • Technical changes and errors excepted.
Page 58
Switching output sends on change to 1 and periodically If switching output = 0 send 0 Switching output sends on change to 0 and periodically Sensors Sewi KNX AQS and Sewi KNX AQS/TH-D • Version: 10.09.2018 • Technical changes and errors excepted.
The parameter is only taken into consideration if the setting via object is ac- tivated below. Please note that the setting "After power supply restoration and pro- Sensors Sewi KNX AQS and Sewi KNX AQS/TH-D • Version: 10.09.2018 • Technical changes and errors excepted.
Page 60
Set the hysteresis independent of the type of threshold value specification. Hysteresis setting in % • absolute Hysteresis in ppm 0...2000; 500 Hysteresis in % of the threshold value 0 … 50; 20 Sensors Sewi KNX AQS and Sewi KNX AQS/TH-D • Version: 10.09.2018 • Technical changes and errors excepted.
Page 61
The behaviour of the switching output on release is dependent on the value of the pa- rameter "Switching output sends" (see "Switching output") Switching output sends on change • Do not send message • Send switching output status Sensors Sewi KNX AQS and Sewi KNX AQS/TH-D • Version: 10.09.2018 • Technical changes and errors excepted.
The status object shows the current status of the output variable (0 = OFF, >0 = ON) and can for example be used for visualisation. Sensors Sewi KNX AQS and Sewi KNX AQS/TH-D • Version: 10.09.2018 • Technical changes and errors excepted.
Determine what the control variable comparator should output, and activate the input objects to be used. Transmission patterns and blocks can also be set. Sensors Sewi KNX AQS and Sewi KNX AQS/TH-D • Version: 10.09.2018 • Technical changes and errors excepted.
Maintain the input values received via communication • never objects • after power supply restoration • after power supply restoration and programming Sensors Sewi KNX AQS and Sewi KNX AQS/TH-D • Version: 10.09.2018 • Technical changes and errors excepted.
Page 66
• 4 byte counter without math. symbol • 4 byte counter with math. symbol • 4 byte floating point Output value (if applicable output value A1 / A2) Sensors Sewi KNX AQS and Sewi KNX AQS/TH-D • Version: 10.09.2018 • Technical changes and errors excepted.
Page 67
0 [Input range depending on the type of is exceeded output] if blocked 0 [Input range depending on the type of output] Sensors Sewi KNX AQS and Sewi KNX AQS/TH-D • Version: 10.09.2018 • Technical changes and errors excepted.
Page 68
Analysis of the blocking object • At value 1: block | At value 0: release • At value 0: block | At value 1: release Sensors Sewi KNX AQS and Sewi KNX AQS/TH-D • Version: 10.09.2018 • Technical changes and errors excepted.
Each logic output may transmit one 1 bit or two 8 bit objects. Determine what the out put should send if logic = 1 and = 0. Sensors Sewi KNX AQS and Sewi KNX AQS/TH-D • Version: 10.09.2018 • Technical changes and errors excepted.
Page 70
Output value object B if 0 … 255 / 100% / 360° / 127; 0 monitoring period is exceeded Sensors Sewi KNX AQS and Sewi KNX AQS/TH-D • Version: 10.09.2018 • Technical changes and errors excepted.
• Do not send message toring time • Send value exceeding [= value of the parameter "monitoring period"] 6.20.2.AND logic connection inputs Do not use Sensors Sewi KNX AQS and Sewi KNX AQS/TH-D • Version: 10.09.2018 • Technical changes and errors excepted.
Page 72
Switching output 2 Temperature inverted Switching output 3 Temperature Switching output 3 Temperature inverted Switching output 4 Temperature Switching output 4 Temperature inverted Sensors Sewi KNX AQS and Sewi KNX AQS/TH-D • Version: 10.09.2018 • Technical changes and errors excepted.
Page 73
Cooling 2 temperature controller inactive Humidity controller dehumidification 1 active Humidity controller dehumidification 1 inactive Humidity controller dehumidification 2 active Humidity controller dehumidification 2 inactive Sensors Sewi KNX AQS and Sewi KNX AQS/TH-D • Version: 10.09.2018 • Technical changes and errors excepted.