NuAire ECOSMART TWINFAN Series Installation And Maintenance Manual

NuAire ECOSMART TWINFAN Series Installation And Maintenance Manual

1 phase, direct drive, run & standby for external, roof mounted and internal use

Advertisement

EST-X
Figure 1. EST-X unit.
A
Removable
top panel
D
Table 1. EST-X Dimensions (mm)
Code
A
B
EST1-X
705
505
EST2-X
875
720
EST3-X
970
720
EST4-X
1165
980
EST5-X
1165
980
EST6-X
1165
980
EST9-X
1495
1125
EST-R & EST-B
Figure 2. EST-R/B units.
Commissioning box
A
Opposed
outlet
grille
C
Control module
located internally
Table 2. EST-R / B Dimensions (mm)
Unit
A
B
C
EST1-R
705
505
355
EST1-B
705
505
355
EST2-R 875
720
400
EST2-B 875
720
400
EST3-R 970
720
485
EST3-B 970
720
485
EST4-R 1165
980
575
EST4-B 1165
980
575
EST5-R 1165
980
575
EST5-B 1165
980
575
EST6-R 1165
980
575
EST6-B 1165
980
575
EST9-R 1495
1125
710
EST9-B 1495
1125
710
T: 029 2085 8400 F: 029 2085 8444 E: info@nuaire.co.uk W: www.nuaire.co.uk
ECOSMART TWINFANS
(EST-X/R/B) 1 phase, Direct Drive,
Run & Standby
Roof Mounted and Internal use
For External,
Installation and Maintenance
B
Control module
located internally
External
Commissioning box
Weight
C
D dia.
(kg)
355
125
22
400
200
35
485
200
50
575
250
72
575
400
75
575
400
86
710
500
162
B
D
Removable
top panel
Circular inlet spigot
on end of unit
F
E
Code: EST*-R
Rectangular bottom
inlet spigot EST*- B only
Weight
D dia.
E
F
(kg)
125
-
-
22
-
76
152
22
200
-
-
35
-
127
229
35
200
-
-
45
-
127
229
45
250
-
-
72
-
152
305
72
400
-
-
75
-
229
457
75
400
-
-
86
-
229
457
86
500
-
-
162
-
304
762
162
Nuaire Limited Western Industrial Estate Caerphilly United Kingdom CF83 1NA
Introduction
Units are rectangular in section and consist of three basic
designs.
Full size access panels are fitted to the top of the units and
are fully detachable for inspection and connection purposes.
The models are coded as follows:
EST-X (External/Internal Duct Mounted) in line unit.
C
EST-R (Roof Mounted, end inlet) side discharge unit.
EST-B (Roof Mounted bottom inlet) side discharge unit.
EST-X units are rectangular in section and have circular rigid
spigots at each end.
EST-R units are rectangular in section and are supplied with
a circular end spigot and two opposed side discharge grilles.
EST-B units are rectangular in section and have a rectangular
bottom spigot and two opposed side discharge grilles.
Handling
Always handle the units carefully to avoid damage and
distortion. If mechanical aids are used to lift the unit, spreaders
should be employed and positioned so as to prevent the slings,
webbing etc. making contact with the casing.
Installation
Installers - please note that Installation must be carried
out by competent personnel in accordance with the
appropriate authority and conforming to all statutory and
governing regulations e.g. I.E.E, CIBSE, COHSE.
EST-X/R/B units are suitable for internal or external use.
All units can be installed at any angle up to 60
sloping roof the unit must be blowing upwards toward the
roof ridge to ensure correct backdraught shutter operation.
Units should always be positioned with sufficient space to
allow removal of the access cover and subsequent removal
of fan and motor assemblies etc.
Whether internally or externally mounted, the method of fixing
to the roof is the responsibility of the installer.
All units have a bottom skirt to allow for fixing directly onto
a suitably sized curb or builders upstand. Nuaire can supply a
matching prefabricated curb for these units. Details of curbs
and dimensions for a suitable external concrete upstand are
shown on page 2.
Ductwork connections must be airtight to prevent any loss of
performance.
In High humidity applications above 90%
trickle ventilation is recommended.
1
The EMC Directive
2014/30/EU
The Low Voltage
directive
2014/35/EU
o
however, on a
16. 06. 15. Leaflet Number 671142

Advertisement

Table of Contents
loading

Summary of Contents for NuAire ECOSMART TWINFAN Series

  • Page 1 EST6-R 1165 EST6-B 1165 EST9-R 1495 1125 EST9-B 1495 1125 Nuaire Limited Western Industrial Estate Caerphilly United Kingdom CF83 1NA T: 029 2085 8400 F: 029 2085 8444 E: info@nuaire.co.uk W: www.nuaire.co.uk 16. 06. 15. Leaflet Number 671142...
  • Page 2: Installation And Maintenance

    (inclusive of the timber capping if applicable, see curb NOTE: A Commissioning Procedure document (leaflet No. dimensions). 671154) is available on request from the Nuaire Technical This mounting height provides adequate distance to avoid any Library Tel: 02920 885911. standing water on the roof being drawn into the fan (this can...
  • Page 3: Electrical Detail

    Motor Electrical Information Table 5. Isolation - Before commencing work make sure 230V single phase 50Hz only that the unit, switched live and Nuaire control are Unit Fuse electrically isolated from the mains supply. Code rating...
  • Page 4: Setting The Airflow

    NOTE: A Commissioning Procedure document (leaflet No. i) Ensure the power supply is switched off and that a link wire 671154) is available on request from the Nuaire Technical is connected from the supply L to the SL terminal. Unplug all Library Tel: 02920 885911.
  • Page 5: Replacement Of Parts

    Check that the impeller rotates freely. Refit the assemblies to the unit (see Replacement of Parts) then replace the access cover. If Nuaire controls and or remote indicators are fitted, remove the cover and carefully clean out the interiors as necessary. Check for damage.
  • Page 6 The equipment referred to in this Declaration of Incorporation is supplied by live are not prevented by the equipment panels or by fixed installation detail Nuaire to be assembled into a ventilation system which may or may not include (eg ducting), then guarding to the appropriate standard must be fitted.
  • Page 7 Installation and Maintenance ECOSMART Direct Drive Roof Mounted Twinfans Notes 16. 06. 15. Leaflet Number 671142...
  • Page 8 Installation and Maintenance ECOSMART Direct Drive Roof Mounted Twinfans Western Industrial Estate Caerphilly United Kingdom CF83 1NA T: 029 2085 8400 F: 029 2085 8400 E: info@nuaire.co.uk W: www.nuaire.co.uk 16. 06. 15. Leaflet Number 671142...

This manual is also suitable for:

Ecosmart twinfan est-x seriesEcosmart twinfan est-r seriesEcosmart twinfan est-b seriesEcosmart twinfan est1-xEcosmart twinfan est3-xEcosmart twinfan est2-x ... Show all

Table of Contents