Download Print this page

M-system R5-NE1 Instruction Manual page 8

Ethernet interface module

Advertisement

I/O DATA DESCRIPTIONS
The data allocations for typical I/O modules are shown below.
Refer to the manual for each module for detailed data allocations.
■ 16-BIT ANALOG DATA (models: R5-SV, YV, DS, YS, RS, TS, etc.)
0 to 100% of the selected I/O range is converted into 0 to 10000 (binary).
With °C or Kelvin temperature unit, raw data is multiplied by 10. For example, 25.5°C is converted into 255.
With °F temperature unit, the integer section of raw data is directly converted into the data. For example, 135.4°F is con-
verted into 135.
Negative values are represented in 2's complements.
15
■ 4-POINT DISCRETE DATA (models: R5-DA4, DC4, etc.)
15
0 : OFF
1 : ON
■ 16-POINT DISCRETE DATA (models: R5-DA16, DC16, etc.)
15
0 : OFF
1 : ON
0
0
Input 1 (Output 1)
Input 2 (Output 2)
Input 3 (Output 3)
Input 4 (Output 4)
Not Used (Remains "0")
0
Input 1 (Output 1)
Input 2 (Output 2)
Input 3 (Output 3)
Input 4 (Output 4)
Input 16 (Output 16)
5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: info@m-system.co.jp
R5-NE1
EM-6111 Rev.10 P. 8 / 8

Advertisement

loading