Download Print this page

M-system R5-NE1 Instruction Manual page 6

Ethernet interface module

Advertisement

DATA ALLOCATION MODE
The DIP SW located at the side of the module switches the unit's data allocation mode.
The Data Allocation Mode 1 is used when all analog I/O modules are single-channel types. In this mode, one (1) word is as-
signed for one I/O module. The second channel on the dual-channel modules cannot be used.
The Data Allocation Mode 2 is used when one or more analog I/O modules are dual-channel types. In this mode, two (2) words
are assigned for one I/O module regardless of whether the second word area is required or not.
For discrete I/O, 16-channel area is automatically assigned to each module. For example, with a 4-channel module, the bits
assigned to ch. 5 through 16 remain "0."
MODBUS I/O ASSIGNEMNTS
Coil (0X)
1 – 16
17 – 32
33 – 48
49 – 64
:
241 – 256
Inputs (1X)
1 – 16
17 – 32
33 – 48
49 – 64
:
241 – 256
257 – 272
273 – 288
289 – 320
■ Data Allocation Mode 1
Input Registers
1
(3X)
2
3
4
:
16
17, 18
19, 20
21, 22
23, 24
:
47, 48
Holding Registers
1
(4X)
2
3
4
:
16
17, 18
19, 20
21, 22
23, 24
:
47, 48
Note: DO NOT access addresses other than mentioned above. Such access may cause problems such as inadequate operation.
Module 1
Do 1 – 16
Module 2
Do 1 – 16
Module 3
Do 1 – 16
Module 4
Do 1 – 16
:
:
Module 16
Do 1 – 16
Module 1
Di 1 – 16
Module 2
Di 1 – 16
Module 3
Di 1 – 16
Module 4
Di 1 – 16
:
:
Module 16
Di 1 – 16
Active Module Map
Status
Channel Status
Module 1
Ai 1 (INT)
Module 2
Ai 1 (INT)
Module 3
Ai 1 (INT)
Module 4
Ai 1 (INT)
:
:
Module 16
Ai 1 (INT)
Module 1
Ai 1 (Float)
Module 2
Ai 1 (Float)
Module 3
Ai 1 (Float)
Module 4
Ai 1 (Float)
:
:
Module 16
Ai 1 (Float)
Module 1
Ao 1 (INT)
Module 2
Ao 1 (INT)
Module 3
Ao 1 (INT)
Module 4
Ao 1 (INT)
:
:
Module 16
Ao 1 (INT)
Module 1
Ao 1 (Float)
Module 2
Ao 1 (Float)
Module 3
Ao 1 (Float)
Module 4
Ao 1 (Float)
:
:
Module 16
Ao 1 (Float)
5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: info@m-system.co.jp
■ Data Allocation Mode 2
Input Registers
1
(3X)
2
3
4
:
31
32
33, 34
35, 36
37, 38
39, 40
:
93, 94
95, 96
Holding Registers
1
(4X)
2
3
4
:
31
32
33, 34
35, 36
37, 38
39, 40
:
93, 94
95, 96
R5-NE1
Module 1
Ai 1 (INT)
Module 1
Ai 2 (INT)
Module 2
Ai 1 (INT)
Module 2
Ai 2 (INT)
:
:
Module 16
Ai 1 (INT)
Module 16
Ai 2 (INT)
Module 1
Ai 1 (Float)
Module 1
Ai 2 (Float)
Module 2
Ai 1 (Float)
Module 2
Ai 2 (Float)
:
:
Module 16
Ai 1 (Float)
Module 16
Ai 2 (Float)
Module 1
Ao 1 (INT)
Module 1
Ao 2 (INT)
Module 2
Ao 1 (INT)
Module 2
Ao 2 (INT)
:
:
Module 16
Ao 1 (INT)
Module 16
Ao 2 (INT)
Module 1
Ao 1 (Float)
Module 1
Ao 2 (Float)
Module 2
Ao 1 (Float)
Module 2
Ao 2 (Float)
:
:
Module 16
Ao 1 (Float)
Module 16
Ao 2 (Float)
EM-6111 Rev.10 P. 6 / 8