2.2 Specification

ITEM
General
Power source
Operating ambient temperature
Storage ambient temperature
Operating ambient humidity
Storage ambient humidity
Vibration resistance
Noise resistance
Dielectric withstand voltage
Consumption current
Usage environment
Structure
Cooling
Function
Number of I/O modules
Node address range
IN + OUT data
IN data update cycle time
Data transfer rate :
Max segment length
Self-diagnosis
GSD file
Chapter 2 STRUCTURE and SPECIFICATION
Supplied from power Supply Module
0 to 55 degree
-10 to 75 degree
No condensation 20 to 90 % RH
No condensation 10 to 90 % RH
In accordance with JIS C 0911
¡Noise voltage 1500 Vpp Noise pulse with 100 ns, 1µs by using
noise simurator.
¡Based on NEMA ICS 3-304 (with the exception of input module)
¡Static noise : 3000 V at metal exposed area
250 V DC between External signal terminal and FE terminal
5 V DC 600 mA
No corrosive gasses, no excessive dirt
Attaches to an open wall
Natural air cooling
16
1 - 99
208 words
5 ms
9.6
kbps
: 1200 m
19.2
kbps
: 1200 m
93.75
kbps
: 1200 m
187.5
kbps
: 1000 m
500
kbps
:
1500
kbps
:
3
M bps
:
6
M bps
:
12
M bps
:
System ROM/RAM check,
watch-dog timer check
File name : hita049d.gsd
This file can either be downloaded from the webpage
http://www.hms.se/fbfiles.htm
HMS Fieldbus AB.
2-2
SPECIFICATION
400 m
200 m
100 m
100 m
100 m
or received by contacting