SYMPTOM 
 
故障現象
Main flame lights but 
extinguishes.  Burner locks out 
at main flame. 
 
主火焰點燃後熄滅,燃燒器在 主
火焰時報警。。
Main flame reaches high fire 
but extinguishes.  No lockout. 
 
主火焰到達高火後熄滅,沒有 報
警。
Main flame extinguishes 
during steady fire.  Burner 
locks out at normal run. 
 
在火焰穩定期間,主火焰熄
滅。燃燒器在正常運行時報警 切
斷。
Burner locks out at normal 
shutdown 
 
燃燒器在正常停機時報警
 
POSSIBLE CAUSE 
 
故障原因
Low gas pressure switch 
a) 
set high 
低燃氣壓力開關設定太高
 
b) High gas pressure switch 
set low 
高燃氣壓力開關設置太低
 
c) Pilot setting high 
點火火焰太大
 
d) Flame undetected 
火焰未被探測到
a)    High or low gas pressure 
switch faulty 
高/低燃氣壓力開關失靈
 
Process pressure switch 
b)    
faulty 
工藝空氣壓力開關失靈
 
c) Process pressure low 
工程空氣壓力過低
 
d) Interlock circuit broken 
鎖回路斷路
a) Loss of gas supply 
燃氣供應不足
 
b) Loss of combustion air 
燒空氣不足
c) Failure of flame detector 
火焰探測器故障
a)    Automatic gas shutoff 
valves not closing fully 
動燃氣安全關斷閥沒有關
斷到位
13
REMEDY 
 
補救措施
a) Reset gas pressure switch 
重新設置燃氣壓力開關
 
b) Adjust pilot rate 
點火火焰調節
 
c) Reposition flame 
detection 
改變火焰探測位置
a) Replace gas pressure 
switch 
更換燃氣壓力開關
 
b) Check process fan 
檢查工藝風機
 
c) Reinstate interlock 
修理聯鎖裝置
a) Restore gas supply 
恢復燃氣供應
 
b) Restore combustion air 
複燃燒空氣
c) Replace flame detector 
換火焰探測器
a)    Isolate gas at manual 
valve repair or replace 
automatic valve 
用手動閥隔離燃氣。修理
或更換安全關斷閥
08092018