IFM TAD 81 Series Operating Instructions Manual

IFM TAD 81 Series Operating Instructions Manual

Temperature transmitter

Advertisement

Quick Links

Operating instructions
Temperature transmitter
UK
TADx81
TADx91

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the TAD 81 Series and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for IFM TAD 81 Series

  • Page 1 Operating instructions Temperature transmitter TADx81 TADx91...
  • Page 2: Table Of Contents

    Contents 1 Preliminary note ���������������������������������������������������������������������������������������������������3 1�1 Symbols used ������������������������������������������������������������������������������������������������3 2 Safety instructions �����������������������������������������������������������������������������������������������3 3 Getting started �����������������������������������������������������������������������������������������������������4 4 Functions and features ����������������������������������������������������������������������������������������5 5 Function ���������������������������������������������������������������������������������������������������������������5 5�1 IO-Link �����������������������������������������������������������������������������������������������������������6 5�2 Analogue function ������������������������������������������������������������������������������������������6 5�3 Diagnostic function ����������������������������������������������������������������������������������������8 5�3�1 Drift monitoring ������������������������������������������������������������������������������������8 5�3�2 Sensor backup (redundancy switching) ������������������������������������������������9 5�3�3 Diagnostic cases ��������������������������������������������������������������������������������10 5�3�4 Diagnostic function in 2-wire operation �����������������������������������������������10...
  • Page 3: Preliminary Note

    11 Fault correction ������������������������������������������������������������������������������������������������21 12 Factory setting �������������������������������������������������������������������������������������������������22 1 Preliminary note Technical data, approvals, accessories and further information at www�ifm�com� 1.1 Symbols used ► Instructions > Reaction, result […] Designation of keys, buttons or indications → Cross-reference Important note Non-compliance may result in malfunction or interference�...
  • Page 4: Getting Started

    • Only use the product for its intended purpose (→ 4 Functions and features)� • Only use the product for permissible media (→ 10 Technical data)� • If the operating instructions or the technical data are not adhered to, personal injury and/or damage to property may occur�...
  • Page 5: Functions And Features

    7� Configure switching signal for diagnostic case (only 3-wire operation without IO-Link) - [dOU1]: Output opens / closes / pulsates; according to setting Table 3 → 5.3.5� 8� Configure output logic for diagnostic output (only 3-wire operation without IO- Link) - [P-n]: pnp or npn 9�...
  • Page 6: 5�1 Io-Link

    The IODDs necessary for the configuration of the unit, detailed information about process data structure, diagnostic information, parameter addresses and the necessary information about the required IO-Link hardware and software can be found at www�ifm�com� 5.2 Analogue function The unit converts the measured temperature value into a temperature-proportional analogue signal�...
  • Page 7 4���20 mA with setting [OU2] = I or 20���4 mA with setting [OU2] = Ineg� The measuring range is scalable: • [ASP] defines at which measured temperature value the analogue signal is 4 mA (OU2 = I) or 20 mA (OU2 = Ineg)� •...
  • Page 8: 5�3 Diagnostic Function

    5.3 Diagnostic function By measuring with two different, thermically coupled sensor elements (NTC, PT 1000) the unit automatically detects drifts and errors during temperature measurement� A mean average value is formed from the measured individual NTC and Pt 1000 values� This mean value is the basis for the provided measured temperature value and also the basis for the diagnostic messages with the drift monitoring (→...
  • Page 9: 5�3�2 Sensor Backup (Redundancy Switching)

    There would not be an alarm message� Setting range for drW / drA → 10.1 Due to the usual manufacturing tolerances a temperature difference of max� 0�1 K can also occur with new sensor elements� This does not affect the drift monitoring function�...
  • Page 10: 5�3�3 Diagnostic Cases

    5.3.3 Diagnostic cases Diagnostic messages Diagnostic case Warning Alarm Failure ● 1 Drift warning threshold [drW] exceeded Limit temperature internal electronics ● exceeded (+125°C) ● 3 Drift alarm threshold [drA] exceeded Failure of one of the two sensor ● elements Measured temperature value far ●...
  • Page 11: 5�3�5 Diagnostic Function In 3-Wire Operation

    Diagnostic messages Diagnostic cases [drEd] Warning Alarm Failure (→ 5.3.3) ● = ON 6���9 ● ● = ONdr 3���9 ● ● ● = OFF 1���9 Table 2: Setting of diagnostic cases to be signalled (2-wire operation) - Setting [drEd] = ON provides maximum availability since the transmission of the measured temperature value is only interrupted for the diagnostic message in diagnostic cases of category "failure"�...
  • Page 12 Diagnostic messages Diagnos- tic cases [drEd] Output Warning Alarm Failure (→ 5.3.3) ● = ONdr Analogue output 6���9 ● ● Switching output* 3���9 ● = OFF Analogue output 6���9 ● ● ● Switching output* 1���9 Table 3: Setting of diagnostic cases to be signalled (3-wire operation) * physical switching output as well as a switching output simulated via IO-Link�...
  • Page 13: 5�3�6 Process Data Transmission In Io-Link Operation

    — Measured value of the remaining sensor element continues to be provided� For the failed element, "NoData" is displayed instead of the measured value� "Invalid" is provided instead of the measured value� List of all diagnostic cases readable via IO-Link (events and errors) → IO Device Decription (IODD) at www.ifm.com.
  • Page 14: Installation

    ► Insert the unit with process adapter into the process connection and tighten using a spanner� Information about available adapters at www�ifm�com� ► Observe the instructions of the adapter� ► Use a lubricating paste which is suitable and approved for the application�...
  • Page 15: 6�1�3 Installation Using A Process Adapter With Metal-To-Metal Seal

    6.1.3 Installation using a process adapter with metal-to-metal seal Order no� E337xx / E338xx A long-term stable and maintenance-free fitting without bug traps in the metal-to- metal seal is only valid for once-only mounting� If the sealing has to be installed several times, use a new adapter� 6.1.4 Installation to G 1 flange The process is sealed with the sealing ring at the back of the sensor�...
  • Page 16: 6�4 Use In Hygienic Areas To Ehedg

    6.4 Use in hygienic areas to EHEDG The sensor is suited for CIP (cleaning in process) when installed correctly� ► Observe the application limits (temperature and material resistance) according to the data sheet� ► Make sure that the sensor is integrated into the system according to EHEDG: ►...
  • Page 17: Electrical Connection

    7 Electrical connection The unit must be connected by a qualified electrician� The national and international regulations for the installation of electrical equipment must be adhered to� Voltage supply to EN 50178, SELV, PELV / "supply class 2" to cULus� ►...
  • Page 18: 8�1 Adjustable Parameters

    ► Connect the unit via the IO-Link interface to a PC or PLC with suitable parameter setting software� IO-Link interface for connection of the sensor to a PC → www.ifm.com. 8.1 Adjustable parameters Setting of the standard unit of measurement: °C or °F�...
  • Page 19: Operation

    8 s (= normal operating mode)� It carries out its measurement and evaluation functions and provides output signals according to the set parameters� 10 Technical data Technical data and scale drawing at www�ifm�com� 10.1 Setting range for drW / drA Medium temperature Setting range -10���100 °C...
  • Page 20 [°C] [°F] 1: x = minimum value for drW and drA 2: Medium temperature If the value that has been set for drW or drA is lower than the value x, the sensor will change it automatically to the value x� In case of operation in gaseous media the value should be greater than 0�35 °C / 0�6 °F�...
  • Page 21 11 Fault correction In case of faults or anomalies: ► Connect the unit to a PC and read [Fnr] via the IO-Link interface� ► Read [Fnr]� Fnr Type of fault Corrective measures No fault, no anomaly occurred� Internal malfunction in the sensor ►...
  • Page 22 Fnr Type of fault Corrective measures Supply voltage outside the operating ► Check the supply voltage; ensure a voltage range� correct voltage supply� Operating temperature of the electronics ► Check the temperature of the upper outside the specified range� part of the unit� ►...