RWD45U Controller Installation and Commissioning Guide
Initial Program
Settings
(New Controller)
PS 1 – Application Settings
Enter application number
Select number of compressor stages
Select reversing valve output – On or Off during no demand
After completing PS1, the user has the option to progress to setpoint mode (only for new RWD) by waiting for
two seconds and default parameters will be accepted. If parameters PS2 through PS4 need to be adjusted,
press the + σ button immediately to the next PS (see Commissioning Flowchart).
PS 2 – Input X1, X2 and X3
Select unit
Select main sensor X1
Enter X1 sensor calibration offset (Ni or Pt only)
Enter X1 active sensor range (0 to 10 Vdc only)
Select auxiliary sensor X2
Enter X2 sensor calibration offset (Ni or Pt only)
Enter X2 active sensor range (0 to 10 Vdc only)
Select sensor X3 (for Economizer sensor)
Enter X3 sensor calibration offset (Ni or Pt only)
Enter X3 active sensor range (0 to 10 Vdc only)
Select unit for X3 (for Independent control sensor)
Select X3 sensor
Enter X3 sensor calibration offset (Ni or Pt only)
Enter X3 active sensor range (0 to 10 Vdc only)
PS 3 – Digital, Auxiliary Function, Eco and Ind. (Y)
Select digital input D1
Aux. Function = Setpoint reset
Setpoint reset start point, reverse acting
Setpoint reset end point, reverse acting
Setpoint reset shift
Setpoint reset start point, direct acting
Setpoint reset end point, direct acting
Setpoint reset shift
Aux. function = WIN SUM analog
Enter changeover setpoint for winter
Enter changeover setpoint summer
Enter changeover time delay, winter ⇔ summer
Siemens Industry, Inc.
There are five levels of parameter setting (PS) modes: PS1 through PS4, and a
setpoint mode. Each PS has a set of default parameters, which can be changed during
commissioning.
When powered the first time, the controller will proceed to PS1 with default
application 10. See below for commissioning steps.
Document Number 129-409
Range/Type
10 through 99
1-, 2- or 3-stage
On or Off
Range/Type
°F or °C
Ni1000, Pt1000, 0 to 10V
± 5 K
-100 to 2400
Ni1000, Pt1000, 0 to 10 Vdc
± 5 K
-100 to 2400
Ni1000, Pt1000, 0 to 10 Vdc
± 5 K
-100 to 2400
C, F, %, -----, or
X1 32°F to 122°F (0°C to
50°C) ⇒ Y1 (0 to 10 Vdc)
Ni1000, Pt1000, 0 to 10 Vdc
± 5 K
-100 to 2400
Range/Type
D/N, Filter Alarm, Alarm, on/off
Setpoint reset sensor range
Setpoint reset sensor range
Setpoint reset sensor range
Setpoint reset sensor range
Setpoint reset sensor range
Setpoint reset sensor range
Sensor range
Sensor range
00.01 to 23 Hrs 59 min
October 5, 2009
Default
10
2-stage
Off
Default
°F
Ni1000
0 K
32°F to 122°F
(0°C to 50°C)
Ni1000
0 K
32°F to 122°F
(0°C to 50°C)
Ni1000
0 K
32°F to 122°F
(0°C to 50°C)
F
Ni1000
0 K
32°F to 122°F
Default
Depends on #x
72°F (22°C)
64°F (18°C)
4K
82°F (28°C)
90°F (32°C)
4K
72°F (22°C)
82°F (28°C)
00.01
Page 7 of 13