Detail.screen; Component.test.screen - Pro Refrigeration TS110 Manual

Table of Contents

Advertisement

Details Screen
The Details Screen contains a fully customizable set of set of
fields specific to the selected compressor circuit. The top row
displays the time, Pervious Button, Next Button, the com-
pressor number you are viewing and the mode of it's refriger-
ation circuit. The remaining rows display Discharge Pressure
(Dis P), Suction Pressure (Suc P), Suction Superheat (Suc
SH), Set Point Button (SP), Outlet Temperature (Outlet),
Inlet Temperature (Inlet), Output Percentage (Out), Output
Status (Output Status), Input Status (Input Status), Lead
Compressor (Lead). See Figure 4-4.
Figure 4-4 Details Screen
•Previous Button: The Previous button will take you
back to the Home Screen.
•Next Button: The Next button will take you to the
Component Test Screen.
•Set Point Button: By tapping the set point button
on the Details Screen you can adjust the set point for
compressor circuit you have selected. A numerical
keypad will popup, tap the value of the desired set point
and tap "Enter". The SP value will update on the Home
Screen. See Figure 4-3.
•Reset Button: By tapping the RESET button you
will reset the current operation mode of the CR110.
This will clear any CR110 alarms if the source of the
alarm has been corrected.
TS110 Screen & Operation Overview |
Component Test Screen
The Component Test Screen allows you to manually power
on the CR110 outputs to each component within the se-
lected circuit. See Figure 4-5.
Caution: The buttons on this screen should
be used only as electrical verification prior to
system operation. Do not use while system is
running.
Figure 4-5 Component Test Screen
•Previous Button: The Previous button will take you
back to the Details Screen.
•Next Button: The Next button will take you to the
System Parameters Screen.
•C Fan 1 Button: Energizes CR110 output for con-
denser fan 1.
•C Fan 2 Button: Energizes CR110 output for con-
denser fan 2.
•C Fan 3 Button: Energizes CR110 output for con-
denser fan 3.
•Circ P 2 Button: Energizes CR110 output for circula-
tion pump 2.
•COMP 2 Button: Energizes CR110 output for com-
pressor 2.
•LLS Button: Energizes CR110 output for the liquid
line solenoid valve.
•UL1 Button: Energizes CR110 output for compressor
unloader 1.
•UL2 Button: Energizes CR110 output for compressor
unloader 2.