Air Purifying Control [Detection Of Abnormality]; Discharge Temperature Control - Toshiba RAS-10GAVP-E Service Manual

Toshiba air condition service manual
Hide thumbs Also See for RAS-10GAVP-E:
Table of Contents

Advertisement

Item
Operation flow and applicable data, etc.

12. Air purifying control [Detection of abnormality]

Purifying operation
YES
Total operation
time 1000H
Purifier power ON
Error input
Purifier power ON
1 minute or less
Filter lamp ON
Purifier power OFF
Filter lamp ON
Purifier power OFF
1
1) Reset by RESET button.
2) Reset by RESET button or by the stop direction
from the remote controller.
* When the breaker is turned [ON] (In restart time
after power failure) or RESET button is pressed
while the FILTER indicator is turned on, the air
purifier is not turned on until the integrated
operation time of the indoor fan exceeds 1 hour
after operation start (It is nor the air purifier
operation time).
It is the safety measures considering an incom-
plete drain when electric dust collector has been
cleaned with water.

13. Discharge temperature control

Td value
Judges as an error and stops the compressor.
117°C
Reduce the compressor speed.
112°C
Reduce slowly compressor speed.
108°C
Keeps the compressor speed.
105°C
If the operation is performed with lower speed than one
commanded by the serial signal, speed is slowly raised
up to the commanded speed.
98°C
Operates with speed commanded by the serial signal.
NO
NO
YES
NO
Filter lamp-OFF
continues.
YES
Purifier power OFF
Purifier power ON
after 10 minutes
from the error input.
Error input
Purifier power OFF
2
Control operation
1. Purpose
The air purifying control function is to
alert the user to trouble in the ionizing or
air purifying operation.
2. Description
Trouble is determined to have occurred
(indicated by the FILTER indicator) in the
following four cases.
1) When a count of 1000H has been
2) When the panel switch has been set to
3) When an abnormal discharge caused
4) When the electric dust collector has
3. Operation
The sequence that FILTER indicator is
NO
turned on are described in the left
flowchart.
YES
1) When 1000H timer counts up, the
3
2) A trouble detected within 1 minute
3) In case that 1 minute passed after
1. Purpose
This function detects error on the
refrigerating cycle or error on the com-
pressor, and performs protective control.
2. Operation
• Control of the compressor speed
– 37 –
Description
reached on the timer
OFF by the opening of the air inlet
grile, etc.
by a symptom such as the build-up of
dirt has been detected while the air
purifier is ON
not been installed correctly
* Trouble case (2) or (3) is deemed to
have occurred when the action
concerned continues for more than
one second.
FILTER indicator keeps lighting even if
the operation is stopped by the remote
controller.
The timer is stored in memory of the
microcomputer, and the operation time
is cleared by filter RESET button on
the indoor unit or a power failure.
(FILTER indicator goes off.)
after activation of the air is immedi-
ately judged as an error and the
FILTER indicator goes on.
activation of the purifier, the purifier is
turned off while the PURE indicator
keeps ON. After 10 minutes passed,
restart the purifier and an error is
judged again.
The speed control is performed as
described in the left table based upon
the discharge temperature.

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents