Initial Start-Up Of Machine - WATERKOTTE EcoTouch DS 5050T Planning And Installation

2-power levels 0 % - 50 % - 100 %
Table of Contents

Advertisement

Commissioning

10.2 Initial start-up of machine

04.12.2015
Warning! Risc of electric shock!
The unit must be grounded. Do not connect the ground wire to gas or wa-
ter lines, lightning rods or telephone grounding lines. Improperly grounded
unit poses a risk of electric shock.
Risk of injury!
Rotating, hot, or high voltage parts can cause injury.
Risk of injury!
Do not touch the refrigerant pipes during operation with bare hands. The
refrigerant pipes are hot or cold depending on the condition of the flowing
refrigerant. When touching the tubes there is a risk of burns or frostbite.
Use circuit breakers (ground fault interrupter, isolating switch (+ B fuse), and
molded case circuit breaker) with the specified capacity. If the circuit break-
er capacity is larger than required, this can have a system failure or fire may
result.
Figure 1: ON / OFF switch (see pointing arrow)
Switch lights => Power on (normal operation))
The initial start of the heat pump is performed by a qualified WATERKOTTE
system partner. After all checks have been conducted, proceed as follows:
1. Place main switch and all LS switches (control voltage, compressor
and electrical heating element) in position OFF (no light).
2. Place LS switch for control voltage in
position I (switching on).
3. Place main switch on unit in position I (switching on).
4. Now perform controller setting according to WWPR operating
manual.
32 / 48
Copyright  2014 by: WATERKOTTE GmbH. Subject to changes.

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents