For fields *43 and *45:
Enter 0–9; #+11 for B; #+12 for C; #+13 for D; #+14 for E; [#+15 for F]. To clear entries from field, press * 43 * or * 45 * .
Examples: For Acct. 1234, enter:
43 SUBSCRIBER ID # (Part.1)
45 SUBSCRIBER ID # (Part. 2)
47
PHONE SYSTEM SELECT
48
REPORT FORMAT
49
SPLIT/DUAL REPORTING
50
15 SEC DIALER DELAY (BURG)
✱ 53
MISC. FAULT DELAY TIME
(Zone Type 25 or Configurable Zone Type)
✱ 54
DYNAMIC SIGNALING DELAY
✱ 55
DYNAMIC SIGNALING PRIORITY
TO PROGRAM SYSTEM STATUS, & RESTORE REPORT CODES ( ✱ 59 – ✱ 76, & ✱ 89) FOR CONTACT ID® REPORTING:
Enter any digit (other than "0") in the first box, to enable zone to report (entries in the second boxes will be ignored).
UL: see installation instructions for requirements
SYSTEM STATUS REPORT CODES ( ✱ 59– ✱ 68)
✱ 59
EXIT ERROR REPORT CODE
✱ 60
TROUBLE REPORT CODE
✱ 61
BYPASS REPORT CODE
✱ 62
AC LOSS REPORT CODE
✱ 63
LOW BAT REPORT CODE
✱ 64
TEST REPORT CODE
✱ 65
OPEN REPORT CODE
✱ 66
ARM AWAY/STAY RPT CODE
✱ 67
RF XMTR LOW BAT REPORT CODE
✱ 68
CANCEL REPORT CODE
1 | 2 | 3 | 4
; For Acct. B234, enter: #+11| 2 | 3 | 4
| | | /
| | | | |
| | | /
| | | | |
[3]
[77]
primary
secondary
[0]
[1]
[0]
[0]
[0]
[1]
|
[10]
|
[00]
|
[00]
|
[10]
|
[10]
Part. 1 Part. 2 Common
Away Stay
Away Stay
Part. 1
Part. 2
|
[10]
|
[10]
Entry of a number other than one specified will give unpredictable results.
– 4 –
Enter 4 or 10 digits, depending on selection in *48
Report Format. See box above for entries.
Enter 4 or 10 digits, depending on selection in *48
Report Format. See box above for entries.
If Cent. Sta. IS NOT on a WATS line:
0=Pulse Dial; 1=Tone Dial;
if Cent. Sta. IS on a WATS line:
2 = Pulse Dial ; 3 = Tone Dial
5 = CID using 10-digit subscriber account (ID) no.
7 = CID using 4-digit subscriber account (ID) no.
14 = CID 4-digit account no. with shutdown (# + 14)
15 = CID 10-digit account no. with shutdown (# + 15)
UL: only 4-digit Contact ID format has been evaluated
0 = Disable (Backup report only)
Primary Phone No.
1 = Alarms, Restore, Cancel
2 = All except Open/Close, Test
3 = Alarms, Restore, Cancel
4 = All except Open/Close, Test
5 = All
0 = no UL: must be "0"; 1 = yes
0 = 15 seconds
6 = 2-1/2 min
1 = 30 seconds
7 = 3 min
2 = 45 seconds
8 = 4 min
3 = 60 seconds
9 = 5 min
4 = 90 seconds
#+10 = 6 min
5 = 2 minutes
#+11 = 7 min
UL: may only be used on non-burglar alarm/ non-fire alarm
zones when used in fire and/or UL burglar alarm installation
Delay selectable from 0 to 225 secs in 15-sec
increments.
0 = no delay (both signals sent), 1 = 15 secs,
2 = 30 secs, etc. UL: must be "0"
0 = Primary Dialer first; 1 = Long Range Radio first.
Any non-zero entry enables CID report.
Any non-zero entry in first digit enables CID report.
Any non-zero entry in first digit enables CID report.
Any non-zero entry in first digit enables CID report.
Any non-zero entry in first digit enables CID report.
Any non-zero entry in first digit enables CID report.
Use Scheduling mode to schedule periodic test reports.
[0,0,0]
Any non-zero entry enables CID report for partition.
[0,0,0,0,0,0] A ny non-zero entry enables
Away Stay
Common
Any non-zero entry in first digit enables CID report.
UL: must be enabled if wireless devices are used
Any non-zero entry in first digit enables CID report.
Second Phone No.
Others
Open/Close, Test
All
All
All
#+12 = 8 min
#+13 = 10 min
#+14 = 12 min
#+15 = 15 min
CID report