Setting an indoor unit installation option
(suitable for the condition of each installation location)
1.
Check whether power is supplied or not.
- W hen the indoor unit is not plugged in, there should be additional
power supply in the indoor unit.
2.
The panel(display) should be connected to an indoor unit to receive
option.
3.
Set the installation option according to the installation condition of an air
conditioner.
- The default setting of an indoor unit installation option is
"020010-100000- 200000-300000".
- I ndividual control of a remote controller(SEG20) is the function that controls an
indoor unit individually when there is more than one indoor unit.
4.
Set the indoor unit option by wireless remote controller.
 02 series installation option
SEG1
SEG2
0
2
SEG7
SEG8
1
Drain pump
SEG13
SEG14
2
External control
SEG19
SEG20
Individual control of
3
a remote controller
 1WAY/2WAY/4WAY MODEL : Drain pump(SEG8) will be set to 'USE + 3minute delay' even if the drain
 1 WAY/2WAY/4WAY,DUCT MODEL : N umber of hours using filter(SEG18) will be set to '1000hour' even
if the SEG18 is set to exept for 2 or 6.
 When setting the option other than above SEG values, the option will be set as "0".
 SEG5 central control option is basically set as 1 (Use), so you don't need to set the central control
option additionally.
However, if the central control is not connected but it doesn't indicate an error message, you need to
set the central control option as 0 (Disuse) to exclude the indoor unit from the central control.
SEG3
temperature sensor
/ Minimizing fan
--
operation when
thermostat is off
SEG9
Hot water heater
SEG15
External control
output / External
heater On or Off
signal
SEG21
Heating setting
compensation
EEV Step of stopped
/ Removing
unit during oil return/
condensated water in
heating mode
pump is set to 0.
SEG4
SEG5
External room
Central control
SEG10
SEG11
EEV Step when
--
heating stops
SEG16
SEG17
S-Plasma ion
Buzzer
SEG22
SEG23
Motion detect
sensor
defrost mode
Indoor Unit
1(L)
F2
2(N)
F1
SEG6
FAN RPM
compensation
SEG12
--
SEG18
Number of hours
using filter
SEG24
--
33